SCHLAGEL, INC. 

  

        

VGC-3 Gate Control 

 

 

Page 6 

Service

 

– Manual settings  

Allows the operator to manually change the gate parameters detected during the 

‘Learn Mode’

 routine. A 

password  is  required  to  gain  access  to  this  function.  Press  and  hold  the 

  key  until  the  value  123  is 

displayed, then press the 

Open

 button. You may then change the fully-open wheel count and the motor 

direction (0 or 1). 

Duty Check*

 

– Diagnostic function  

Check  the  adjustment  of  the wheel sensor. This number should be between 00% and 70%. The second 
number shown is the number of increments to a full open position.

 

 * Caution! 

The gate will move when these options are selected.

 

 

A VGC system consists of the VGC Operator Control, a motor power module and a barrier relay. These 
may be located in remote areas of the facility. Determining the cause of the problem may require attention 
to any or all of these areas. The two most common problems are the loss or interruption of power or a 
mechanical problem at the gate. 

The error message on the display is helpful in resolving the problem. 

Fatal Error - 

Three attempts were made to move the gate but were unsuccessful. Most likely this 

is caused by mechanical interference in the gate but could also be an improperly adjusted wheel 
sensor on the gear reducer. 

Closing Error - 

This happens after the 

CLOSE

 

switch has been pressed, or the power is restored, 

but  the  gate  was  unable  to  find  the  closed  position.  This  too  is  usually  caused  by  mechanical 
interference in the gate but it may also be that the gate closed sensor is improperly adjusted. 

Press the CLOSE switch when ready to try again. 

It may be helpful to manually move the gate back and forth for testing and inspection. Do this by using 
the  Control  Menu  to  select  Manual  Mode.  The  gate  may  then  be  intermittently  moved  using  the arrow 
pushbuttons.  

If the display is lit but it is blank, there may have been a severe power disruption and just powering up the 
control may fix the problem. Remember that after a reset or restoration of power the gate home position is 
lost.  The  gate  will  not  respond  to  any  move  command  except 

CLOSE

,  which  will  reset  its  position 

memory.. 

If that does not fix the problem a qualified maintenance person should look at the gate drive and sensors. 
Sensor adjustment and associated testing is discussed in the installation manual. 

 

Troubleshooting  

 

Содержание VGC-3

Страница 1: ...ting the VGC 3 gate from the Operator Control It assumes the gate has been installed wired and setup so that normal positioning of the gate may begin See the separate VGC Electrical Wiring and Setup m...

Страница 2: ...he gate will follow the arrow keys requested position 6 The CLOSE button will immediately close the gate from any open position The gate will not open again until the OPEN button is pressed regardless...

Страница 3: ...d the gate will open to the preset position and stop In summary when the gate is closed it will not respond to changing the preset percent of opening Pressing the Open button opens the gate to the pre...

Страница 4: ...s of sensor activity when the motor is running it stops backs up a bit and retries forward movement to see if it can break loose or dislodge an obstruction If it is successful it continues to its dest...

Страница 5: ...ed or power is interrupted Net Address Network Setup Enables network communication by selecting a character for the address Setting this character to a blank disables the network for this control Gate...

Страница 6: ...pts were made to move the gate but were unsuccessful Most likely this is caused by mechanical interference in the gate but could also be an improperly adjusted wheel sensor on the gear reducer Closing...

Страница 7: ...position set by the VGC preset number The gate will follow the arrow key changes to the request number as long as the relay contact remains closed When the relay contact opens the gate will close The...

Страница 8: ...rstand how and when control should be transferred Note 1 Roller chain reductions may be used to increase force at the cost of speed 2 LCD screen update slows down below 32 F although gate operation is...

Отзывы: