Schischek RedMax-8-F1 Скачать руководство пользователя страница 1

E X P L O S I O N P R O O F

RedMax - ... - F1

RedMax - ... - SF1

RedMax - ... - BF1

RedMax -  ...  - CTS

RedMax -  ...  - VAS

RedMax-...-F1

www.schischek.com

Schischek GmbH

 Germany, Muehlsteig 45, Gewerbegebiet Sued 5, 90579 Langenzenn, Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

RedMax-S-F1_en

V01 –  29-Jun-2017

Subject to change!

Compact. Easy installation. Universal. Cost effective. Safe.

Product views and applications

Description

Highlights

Safety damper

Ball valve

Throttle valve

Electrical, explosion proof rotary actuators

On-off control mode, 24…240 VAC/DC, 95° angle of rotation incl. 5° pretension

8 Nm, 15 Nm with safety operation: fast spring return < 1 s

ATEX tested in acc. with directive 2014/34/EU for zone 2, 22

RedMax

  ¼ turn actuators  –  

size S

 For all type of gas, mists, vapours and dust for use in zone 2 and 22

 Universal supply unit from 24…240 VAC/DC

5 different motor running times 3–15–30–60–120 s/90°, adjustable on site

 On-off control with spring return function, spring return running time < 1 s/90°

 Ex-i circuit for direct connection of the ...Pro-TT-... safety temperature trigger 

(type ...-BF1)

 2 integrated auxiliary switches, switching at 5° und 85° (type ...-SF1 and ...-BF1)

 100 % overload protected

 Compact design and small dimension (L × W × H = 210 × 95 × 80 mm) 

 Direct coupling to the damper shaft with double square connection 12 × 12 mm

 95° angle of rotation inclusive 5° pretension

 Robust aluminium housing (optional with seawater resistant coating) or in stainless steel

 IP66 protection

 Simple manual override in preparation for comfortable manual override

 Gear made of stainless steel and sinter metal

 Weight only ~ 3,5 kg

 

Integrated heater for ambient temperatures down to −40 °C 

 Integrated safety temperature sensor 

 Integrated equipment for manual adjustment (push button, lamp, switch)

 Preparation for adaptable and adjustable auxiliary switches type ...Switch

The RedMax actuators are a revolution for safety, control and shut-off 
dampers and other motorized applications for HVAC systems in chemical, 
pharmaceutical, industrial and offshore/onshore plants, for use in Ex-areas 
zone 2 (gas) and zone  22 (dust).
Highest protection class (ATEX) and IP66 protection, small dimensions, 
only 3,5 kg weight, universal functions and technical data, an integrated 
heater and an optional stainless steel housing guarantee safe operation 
even under difficult environmental conditions. High quality brushless 
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools or 
equipment are not required. Motor running times are selectable on site. 
The integrated universal power supply is self adaptable to input voltages 
in the range of 24...240 VAC/DC. The actuators are 100% overload 
protected and self locking.

...Max-...-F1

 actuators are equipped with spring return fail safe function. 

Additionally the 

...Max-...-SF1

 and 

...-BF1

 actuators are equipped with 

2 integrated, potential free auxiliary switches each and 

...Max-...-BF1

 

comes with an intrinsically safe tripping circuit for connecting the ...Pro-TT-... 
safety temperature trigger. Standard shaft connection is a double square 
direct coupling with 12 × 12 mm. 
Different accessories are available to adapt auxiliary switches, terminal 
boxes or adaptions for ball valves and throttle valves and other armatures. 

Type 

Torque  

Supply 

Motor running time   

Spring return   Control mode 

Feedback 

Wiring diagram

RedMax-   8 - F1

    8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90° 

< 1 s/90°  On-off   – 

SB 

2.4 + 2.5

RedMax- 15 - F1

  15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90° 

< 1 s/90°  On-off   – 

SB 

2.4 + 2.5

RedMax-   8 - SF1

    8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90° 

< 1 s/90° On-off 2 × aux. switches SB 

2.4/2.5 + 3.2

RedMax- 15 - SF1

  15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90° 

< 1 s/90° On-off 2 × aux. switches SB 

2.4/2.5 + 3.2

RedMax-   8 - BF1

    8 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90° 

< 1 s/90° On-off 2 × aux. sw Ex-i tripping circuit SB 2.4/2.5 +3.2 +7.4

RedMax- 15 - BF1

  15 Nm 

24...240 VAC/DC  3 / 15 / 30 / 60 / 120 s/90° 

< 1 s/90° On-off 2 × aux. sw Ex-i tripping circuit SB 2.4/2.5 +3.2 +7.4

RedMax-  ...  - CTS

  Types as above with aluminium housing and seawater resistant coating (cable glands brass nickel-plated)

RedMax-  ...  - VAS

  Types as above with stainless steel housing for aggressive ambient (cable glands brass nickel-plated)

1 / 4

Содержание RedMax-8-F1

Страница 1: ...pharmaceutical industrial and offshore onshore plants for use in Ex areas zone 2 gas and zone 22 dust Highest protection class ATEX and IP66 protection small dimensions only 3 5 kg weight universal functions and technical data an integrated heater and an optional stainless steel housing guarantee safe operation even under difficult environmental conditions High quality brushless motors guarantee l...

Страница 2: ...100 mA Umin AC DC 12 V Umax Imax DC 48 V 1 A Imin AC DC 5 mA Imin AC DC 100 mA Axle of the actuator Double square 12 12 mm direct coupling 100 overload protected Electrical connection Cable 1 m wire cross section 0 5 mm equipotential bonding 4 mm Connections in hazardous areas require a terminal box Diameter of cable Ø 6 2 mm Ø 6 2 mm Ø 6 2 7 4 mm Ø 9 3 mm 2 cable glands in version SF1 Cable gland...

Страница 3: ...tage or current Ex i intrinsic safe data for temperature trigger ExPro TT T 1 0 Attention During commissioning apply a self adjustment drive Regard duty cycle at motor running times Never use spring return actuators without external load Auxiliary switches see Technical data On off SB 2 4 On off 1 wire SB 2 5 Wiring of integrated auxiliary switches SB 3 2 On off spring return Ex i tripping circuit...

Страница 4: ...tion will be blocked for the rest of the idle period Later the release for the next cycle is made automatically by an internal timing relay 4 Same function is applied on spring return actuators fail safe operation is regarded same as a motor running cycle 5 Trying to use the 1 wire On off methode in switch position 0 and 5 software changes the motor running time temporarily and automatically to 15...

Отзывы: