Schischek InBin-P-100 Скачать руководство пользователя страница 2

Schischek GmbH 

Germany, Mühlsteig 45, Gewerbegebiet Süd 5, 90579 Langenzenn,  Tel. +49 9101 9081-0, Fax +49 9101 9081-77, E-Mail [email protected]

www.schischek.com

E X P L O S I O N P R O O F

2 / 6

Technical data 

CE-Mark 

CE No. 0158 

EMC directive 

2004/108/EC

Low voltage directive 

2006/95/EC

Protection type 

IP66 in acc. to EN 60529

Potential compensation 

external PA-terminal, 4 mm²

Protection Class

 

Class I (grounded), 

 

overload voltage category II acc. EN 61010-1

Approbations

Accessories

MKR

  

Mounting bracket for round ducts up to Ø 600 mm

Kit 2

  

Consists of 2 m flexible pressure tube Ø 6 mm, 2 connection nipples

Kit PTC

 

consisting of 2 connecting tubes Ø 6 mm for tube fittings

Power supply 

24 VAC/DC ± 20%  (19,2…28,8 VAC/DC)  50…60 Hz 

Current, power consumption

 

150 mA, ~ 4 W, internal fuse 500 mAT, without bracket, not removable

Galvanic isolation

 

Supply – output 1,5 kV

Electrical connection 

Terminals 0,14…2,5 mm² at integrated junction box, stripping length 9 mm, torque 0,4…0,5 Nm

Cable entry 

2 ×

 

M16 × 1,5 mm, cable diameter ~ Ø 5…10 mm

 

(

...-CT 

in nickel-plated)

 

Cable entry ...-OCT 

2 ×

 

M20 × 1,5 mm, cable diameter ~ Ø 6…13 mm

 (...-OCT 

in nickel-plated)

 

Display 

LCD with backlight, display for configuration, user guidance, parameter and actual value indication via LEDs 

Control elements

 

3 buttons for configuration

Housing protection 

IP66 in acc. to IEC 60529

Housing material 

Aluminium casting, coated (

...-CT/...-OCT 

= version in Amercoat marine painting, seawater-resistant

 ...-OCT

 = Offshore version)

Dimension / weight

 

L × W × H = 180 × 107 × 66 mm / ~ 950 g

Ambient temperature/-humidity 

20…+50 °C / 0…95 % rH, non condensed

Storage temperature 

 

40…+70 °C

Measuring range 

 

0…100 Pa

Range scalable on site 

 

Minimum measuring range is 5 % of full range = 5 Pa  

Maintenance

 

Maintenance free, nevertheless maintenance must be complied with regional standards, rules and regulations 

Sensor circuit

 

Internal circuit

Sensor

 Piezo-pressure-transmitter

Pressure connection

 

P+ / P

 sleeves Ø 4…6 mm, 

OCT

-version has a Ø 6 mm stainless steel tube connection for clamp ring fittings

Response time of sensor 

T90 / 5 sec.

Accuracy of pressure 

<

 

± 1 % typically, max. ± 5 % of end value ± 1 Pa

Setting range hysteresis

 

0,1 Pa…10 Pa (factory setting 2 Pa) 

Start delay 

5 sec.

Starting bypass time

 

3…240 sec. (via menu adjustable; preset 120 sec.) 

Switch activation delay

 

0...240 sec. (via menu adjustable; preset 0 sec./Off)

Setting zero point 

Via menu, mechanical short circuit of P+ / P

 for the moment of zero point setting

Output switch

 

Potentail free switching contact  

 

Ratings load max.  

0,5 A at 30 VAC/DC  /  0,1 A at 250 VAC / 0,1 A at 220 VDC 

 

Ratings load min.  

10 mW / 0,1 V / 1 mA 

Mechanical life

 

10 × 10

6

 

Electrical life (rated load)

 

100 × 10

3

Wiring diagram (SB)

 

SB 1.0

 

Installation sensor / tubing

 

 Safe  area 

 

InBin-P-100

D.IB-P100-02.01-en

23-Aug-2012

Содержание InBin-P-100

Страница 1: ...connection and cable glands nickel plated screws in stainless steel InBin P 100 OCT as above offshore version seawater resistant with aluminium housing and Amercoat painting stainless steel tubes for clamping ring connection cable glands M20 1 5 mm nickel plated screws in stainless steel Electrical binary pressure or differential pressure switches with adjustable switch activation delay 24 VAC DC ...

Страница 2: ...uttons for configuration Housing protection IP66 in acc to IEC 60529 Housing material Aluminium casting coated CT OCT version in Amercoat marine painting seawater resistant OCT Offshore version Dimension weight L W H 180 107 66 mm 950 g Ambient temperature humidity 20 50 C 0 95 rH non condensed Storage temperature 40 70 C Measuring range 0 100 Pa Range scalable on site Minimum measuring range is 5...

Страница 3: ...ration A Installation commissioning maintenance The cable has to be drawn through the cable gland After electrical connection the cable gland must be fixed tighten IP66 must be fulfilled In acc with operation InBin switches are maintenance free The sensors must not be opened by the customer For electrical connection use the internal junction box Attention Before opening the internal junction box c...

Страница 4: ...steresis select physical unit adjust hysteresis Pa mBar InH2O Menu 6 mode select switching charateristic norm open no norm closed nc Menu 7 Menu 8 Menu 9 Menu 10 Menu 11 Menu 12 Menü 13 Menu 16 Menu 15 lamp select backlight save select save data security select password adjust set 1 select normal sensor interval no yes return default setting on off enter password Menu 14 Menu 1 Preset select appli...

Страница 5: ...set To beware complexity during the parametrisation process the InBin P has several predefined setups which distinguish between its intended application You ll find a detailed desciption of all possible presets in the following section Fan speed monitoring The preset FAN is designed for use in fan speed monitoring applications state output switch 1 normal state output switch 2 optional setpoint 1 ...

Страница 6: ...t 2 Mid range the normal range is between setpoint 1 and setpoint 2 for 2 stage devices only Switching characteristic mid range normally open state output switch 1 normal state output switch 2 optional setpoint 1 normal green green red red setpoint 2 Mid range the normal range is between setpoint 1 and setpoint 2 for 2 stage devices only Switching characteristic down range normally closed state ou...

Отзывы: