Installation and commissioning SET DATAEAGLE X-treme IO 2730
Chapter 4 – Installation of new devices
For optimum sealing it is recommended to tighten all
plugs to a torque of 0.6 Nm (use a suitable torque
wrench).
PE must be connected to the switch cabinet ground!
Without wiring the PE connection, the interference filter
cannot filter out interference pulses on the 24 V DC
power supply line. This can lead to interference, mal-
functions or destruction of the device.
The nominal operating voltage of 24 V DC falls under the
category SELV (safety extra low voltage) and is therefore
not subject to the EU Low Voltage Directive. The use of
other power supplies is not permitted. For connection to
the 230 V AC mains supply, an external LPS plug-in
power supply unit with 12 -24 V DC/1 A output voltage
can be used.
In the input circuit there is a self-healing 3A fuse. This
fuse cannot be exchanged. If the fuse trips, the device
must be removed from the supply voltage for approx. 2
minutes. Please make sure that the supply voltage sup-
plies 9 to 33 V DC before switching on the supply volt-
age again.