VC 1100
Connectors and Interfaces
VC1100E/connect
Version 2
→
© Schenck VIBRO GmbH, D-64273 Darmstadt, November 97
C01 / C02 - C11 / C12
3-1
3 Connectors and Interfaces
Fundamentals
♦
All connections including those for power are inside the hous-
ing.
♦
Feed cables into the housing via feed-through fittings. There
is a total of 3 x PG 13.5 and 9 x PG 9 feed-through fittings; 6
on each side.
The threads are PG9, a standard commonly used in Europe.
Each VIBROCONTROL 1100 comes with two PG9/PG7 ad-
apters. PG9/1/2"-NPT adapters are also available.
Maximum cable size is 1.5 mm
2
(16 AWG).
Use flexible cable only.
♦
Cable ends should have crimp ferrules for a proper connecti-
on to the removable terminal strips. Remove (unplug) the
terminal strips during wiring. VIBROCONTROL 1100 groups
the terminal strips in functional blocks (pickups, remote I/O,
relays, etc.) and each is coded to prevent mix-ups.
Use shielded cables to suppress external RF noise. This is
not necessary for power and relay wiring.
Connect all shields to the screw terminals located on top of
both sides of the internal housing (SE).
♦
Run signal cables a minimum of 0.5 m (20 inches) from po-
wer cables. If you must cross a power cable do so at right an-
gles.
By means of steel flexible tubes, protect signal leads from
mechanical damage and electrical interferences.
Index of Cable Connections and Interfaces:
Inputs:
Terminal:
Page:
Power
19 ... 24
4
Pickup Channel A
37 ... 40
5
Pickup Channel B
41 ... 44
5
Relay Reset
35 ... 36
6