Comment to 4.
AND
Several limit values control one relay. This relay is tripped only if
all limit values are exceeded.
OR
Several limit values control one relay. This relay is tripped if at
least one limit value is exceeded.
Note:
If a measuring channel or a limit value has been set to "not active"
("N") and this limit value is combined with an AND, this logical
condition can never become "true". Therefore the alarm indication
can never be activated.
OK-Monitoring
The OK-Monitoring is used to report malfunctions and/or data
failure of the program and data stores, electric damages or the
failure of the pickup and its connection lines. The monitoring
covers an "External range recording" of the vibration signal. Errors
caused by cable breakage, short circuit or earth fault of the signal
lines are recognized, reported and written into the log book.
Since the OK-Relay is normally energized, the messages are
output in the operating state network ON/OFF.