Installation
Contactors C137/C163/C164/C165 – Installation and Maintenance Instructions
7. Installation
7.1 Mechanical installation
Dimensions and further technical
specifications
The dimensions and further technical specifications are
given in the respective data sheets or in our catalogue.
Refer to our catalogue
B60
.
The catalogue is available under:
https://www.schaltbau.com/en/media-library/
Preliminaries
X
For the fastening of the contactor an appropriate
mounting plate with 4 mounting holes (c) accord-
ing to
Fig. 17
has to be provided.
12
14
11
A2
A1
2
1
a
b
c
Fig. 17: Dimensions and arrangement of the mounting holes
X
Depending on the contactor type, the table be-
low shows measurements (a/b) for the mounting
holes, the screw size (c) and the reqired tightening
torque:
Series
C137 C163 C164 C165
Dimension a [mm]
30
± 0.2
35
± 0.2
40
± 0.2
60
± 0.2
Dimension b [mm]
62
± 0.2
85
± 0.2
105
± 0.2
120
± 0.2
Screw size c
M3
M5
Torque
3 Nm
6 Nm
X
The mounting holes can either be
-
threaded holes (for threaded screws)
-
or through holes (for threaded screws and nuts).
X
The length of the fixing screws has to be deter-
mined according to the constructional conditions.
X
In order to secure the mounting screws against
self-loosening, appropriate screw locking ele-
ments have to be provided. Schaltbau strongly
recommends Schnorr-Washers (or similar) to se-
cure the screws.
Correct mounting positions
The contactors are designed for horizontal or vertical
mounting positions
-
horizontal: main contacts (1) must point upwards
-
vertical: plasma exits (2) must point upwards
Examples for intended mounting positions are shown
in
Fig. 18/(A)
Not permissible are suspended or inverted mounting
position as shown in
Fig. 18/(B)
.
A
B
1
2
1
2
Fig. 18: Examples for intended mounting positions (A) and
not permissible mounting positions (B)