background image

4

the fan casing (see fig. 8). Connection is 
made according to the connection dia-
gram in the terminal box cover.

Check the fan rotation direction once the 
motor is connected. Do this by briefly 
flicking the fan power on and off. It must 
comply with the arrow on the fan casing. 
If the direction is wrong, disconnect the 
main power supply and check the con-
nections.

Reversible fans must be fitted with time 
delays to allow the rotor to become sta-
tionary, before reversing the direction.

4.6 Thermal motor protection

The motor may have thermal protection 
(optional accessory) in the form of a ther-
mistor or bimetallic sensor.
If the thermal protection is set to switch 
off at unexpected temperature rises, it 
must be connected to the security sys-
tem. The system must identify if the mo-
tor is working on emergency duty or not. 
Alternatively, leave the thermal protec-
tion disconnected.

5. Start of operation

5.1 Before start-up

After installation of the axial flow fans 
their correct installation, operation and 
interaction must be established through 
an approval test.
The person responsible for the operation 
of the system must take the initiative for 
this test.
The approval test must be confirmed by 
the person responsible for the operation 
of the system and the documentation 
must be kept and produced whenever 
asked for.
Prior to start of operation check that the 
fan and duct connections are clean and 
free from tools and foreign objects.
Also, check that the electric connections 
meet the prescribed requirements, that 
wire guards fitted on the fan inlet or out-
let side are correctly mounted and that 
the direction of rotation of the fan com-
plies with the arrow-plate (check by 
short-time operation).

5.2 Motors with Y/

Δ

 starting

The relay must be set to the calculated ti-
me.

5.3 Start-up procedure

• Start the fan
• Check that no abnormal noise is 

present.

• Check that the vibration level is 

acceptable. The vibration level at 
the fan operating speed must not 
exceed 7 mm/s RMS, measured 
radially at 2 points, 90º offset and at 
the free shaft end of the motor. 
Otherwise, the fan must be 
balanced. Operation at vibration 
levels exceeding 11 mm/ s RMS* is 
not allowed for fixed fan positions.
Operation at vibration levels 
exceeding 18 mm/s RMS* is not 
allowed for fans on support frames 
or anti-vibration dampers.
* ISO 2954, Requirements for 
instruments for measuring 
vibration severity.

• After 30 minutes of operation check 

that the fan operates normally.

6. Maintenance

Keep the NovAx ACN-ARN fans in 
good operational condition to ensure 
satisfactory function and service life.

6.1 Before maintenance

When the fan is out of operation for rea-
sons of inspection or maintenance, the 
electric system must be switched off and 
protected so that the fan cannot cut in.

6.2 Fan casing

The fan casing requires only ordinary 
cleaning.
Painted casings should be checked regu-
larly and surfaces repaired if necessary.

6.3 Rotor

From the factory, the rotor is supplied 
with blades adjusted to the pitch corre-
sponding to the desired operating point 
(pressure and airflow) at the fan speed in 

Important:

Only fans with inner hubs 
of steel may be run in 
reverse. Reversible 
operation increases risk 
of fan stalling. If the fan 
stalls, the service life is 
shortened.

Important:

The NovAx fans can run 
in reverse for shorter 
periods at speeds up to 
the max. allowable of 
normal direction. The 
airflow is reduced to 
approx. 50% of normal for 
the same system 
resistance. The pressure is 
reduced to 25%.
Reversible fans must be 
fitted with time delays to 
ensure that the rotor is 
completely stationary 
before reversing 
direction.
Running the fans in 
reverse increases the risk 
of stall and shortens fan 
life.

Important:

The fan is designed for 
continuous operation. 
The following kinds of 
operation may cause 
fatigue breaks in the rotor 
and endanger people.

-

Operation in stall area - 
operation with 
pulsating counter 
pressure - called pump 
mode

-

Operation with 
repeated starting and 
stopping.

-

Uneven flow velocity 
through fan.

If in doubt Novenco 

should be contacted to 
assess fan suitability.

Figure 7. Dismounting and mounting of axial flow fan

05

01 02 03 04 06 07

08

09

10 11

14

12

13

Содержание NOVENCO NovAx ACN SMOKE

Страница 1: ...Pure competence in air 918149 0 ACN ARN SMOKE INSTALLATION AND MAINTENANCE ENGLISH ...

Страница 2: ...pplied with approval num ber class or category are also mentioned as well as test standard applied EN 12101 3 Fan pressure air quantity out put and maximum speed per minute are also on the fan nameplates The fan is also provided with a motor nameplate with relevant motor data in cluding insulation class of the motor 2 2 Weight The total weights shown in table 1 apply to axial flow fans type ACN AR...

Страница 3: ...n is provided with an arrow plate denoting the direction of airflow through the fan casing See during instal lation that the fan is oriented so as to pro vide the desired direction of airflow in the system The best way of installing the fan is with asupportframe optionalaccessory but it may also be suspended in the fan cas ing flanges or in special carriers The carriers must not hamper the free in...

Страница 4: ...fig 6 The duct or inlet cone on the fan inlet side must be designed to ensure smooth and undisturbed airflow ACN ARN smokefansarepreparedforcircularduct connection on both inlet and outlet sides Flanges supplied as standard for type ACN ARN comply with Eurovent 1 2 Systems with higher vibration levels or more exacting performance require ments must be provided with expansion joints between fan and...

Страница 5: ... 7 mm s RMS measured radially at 2 points 90º offset and at the free shaft end of the motor Otherwise the fan must be balanced Operation at vibration levels exceeding 11 mm s RMS is not allowed for fixed fan positions Operation at vibration levels exceeding 18 mm s RMS is not allowed for fans on support frames or anti vibration dampers ISO 2954 Requirements for instruments for measuring vibration ...

Страница 6: ...an casing must be the same throughout the circumference If neces sary adjust the motor location in the sus pension arrangement Now mount centre screw item 01 cen tre disc item 02 and hub cover item 03 Replace lock washers or lock nuts during fan assembly Finally connect motor cable item 13 in terminal box item 12 and ducts if any To start the fan follow the procedure de scribed in section 5 Start ...

Страница 7: ... A S AirBox and NovAx are trademarks of Novenco Building Industry A S Other trademarks appearing in this doc ument are the property of their respec tive owners Copyright c 1985 2018 Novenco Building Industry A S All rights are reserved 12 Quality management NovencoBuilding IndustryA SisISO 9001 certified This means that all fans are inspected and tested before leaving the production 13 Warranty No...

Страница 8: ...Pure competence in air WWW NOVENCO BUILDING COM ...

Отзывы: