background image

3

Emergency stops must be installed in 
compliance with current rules and 
legislation.

4.3.1 Access to terminal box

Unscrew the four screws of the 
plate cover (1, fig. 6).

Remove, turn, and fixate the cover 
(2, fig. 6). Keep the terminal box 
attached to the plate cover.

5. Start of operation

The fans are designed for 
continuous operation. The 

below kinds of operation may cause 
fatigue breaks in the impellers and 
endanger people.

Operation in stall area, i.e. with 
counter pressure that pulsates - 
called pump mode

Operation with uninterrupted and 
repeated starts and stops

Uneven flow velocity through the 
fans

Ask Novenco if in doubt.

5.1 Approval for operation

When the jet fans have been mounted 
and are serviceable their function, 
correct installation, and interaction must 
be established through an approval test.
The person responsible for the operation 
of the system must take initiative for this 
test
The approval test must be documented 
and kept by the person responsible for 
the operation of the system and must be 
presented on demand if it concerns jet 
fans approved for smoke control.
Before start-up, check that the fans are 
clean and free from tools and foreign 
substances and that the impellers rotate 
freely.
Check also that the electrical connection 
complies with current regulations and 
that the wire guard of the inlet nozzles 
and the deflector in the outlet are 
installed properly.
The fan rotation direction is checked 
after a brief start. Refer to the arrow signs 
on the side of the fan.
Note, that during the first 30 minutes of 
operation the motor may consume more 
power than stated on the motor plate. 
Also, the current consumption depends 
on the temperature.

5.2 Start procedure

Start procedure

1 Start the fan
2 Check for irregular sounds
3 Check after 30 minutes that the fan 

functions correctly.

6. Maintenance

The user must always keep the jet fans in 
good working order.
To ensure functionality and life of the 
fans the following must be observed.

Shut off and disconnect the fan 
power supply before beginning 
any work or cleaning on the 

fans.

6.1 Safety measures

Ensure that unintentional activation is 
impossible. Cut, for instance, the power 
in the fuse box or use another centrally 
placed power switch. Fans with 
automatic control may suddenly start 
unless the power supply is disconnected.

6.2 Maintenance of fans

6.2.1 CO-fans

For fans used for CO-ventilation yearly 
inspection and check of functionality is 
recommended.

6.2.2 Smoke control fans

Fans approved for smoke control and 
used for ventilation on a daily basis, 
must be inspected every six months.
Fans that are only used in case of fire 
must be inspected four times per year. 
It is important to comply with the motor 
supplier's guidelines for maintenance.

6.3 Cleaning

Clean the cabinet, outlet, motor, inlet and 
wire guard with a wet cloth. A vacuum 
cleaner fitted with a brush or pressurised 
air may also be useful, depending on the 
kind of filth that have settled on the fan 
unit.
The motor and inlet areas require 
removal of the motor and fan wheel 
arrangement. Remove the motor to clean 
the inlet nozzle. It is recommended to 
leave the wire guard on the inlet nozzle, 
as it is riveted to the nozzle. See section 

“6.6 

Removal of motors

.

Do not use high-pressure water 
cleaning.

See section 

“6.7 

Mounting of motors

 for 

reassembly instructions.

Figure 4.

Circuit diagram in motor 
terminal box

Figure 5.

Connections in terminal box

Figure 6.

Access to terminal box

Tw

o speed

(Dahlander)

Max. r/min

Min. r/min

Low speed

High speed

Earth

L1 L2 L3

L1 L2 L3

1

2

Содержание NOVENCO CGF

Страница 1: ...Pure competence in air 922646 0 0 NOVENCO JET FANS TYPE CGF INSTALLATION AND MAINTENANCE ENGLISH...

Страница 2: ...d address are on nameplates together with information such as product type and size serial or order number max RPMs weight production year and compliance markings Also on the jet fan casings are namep...

Страница 3: ...nsion bolts with documented load capacity during fire must be installed and loaded as stated in the approval Mount the jet fan to a horizontal plane with a natural frequency at least 20 from the fan r...

Страница 4: ...temperature 5 2 Start procedure Start procedure 1 Start the fan 2 Check for irregular sounds 3 Check after 30 minutes that the fan functions correctly 6 Maintenance The user must always keep the jet...

Страница 5: ...16 1 fig 8 from the fan casing and take it down The arrangement requires twopeople totakedownsafely Make sure topull the motor cable completely free of the fan casing 6 Leave the wire guard affixed to...

Страница 6: ...lation should be revised Consider additional measures to improve the safety of the installation 11 Reference documentation Please refer to the below documents for further information about the fans Ca...

Страница 7: ...ISO 1461 2009 BS DS EN 1886 2007 BS DS EN ISO 5801 2017 BS DS EN ISO 9001 2015 BS DS EN ISO 12100 2010 BS DS EN 12101 3 2015 BS DS EN 12101 6 2005 AC 2006 BS DS EN ISO 12499 2008 BS DSF FprEN ISO 1275...

Страница 8: ...Pure competence in air WWW NOVENCO BUILDING COM...

Отзывы: