7. Troubleshooting

Fans that operate in the stall 
area are more likely to suffer 
breakdowns.

Check for the below faults in case of 
breakdowns or lack in performance. Call 
for service, if problems persist.

Lack in performance

Blocked

Inlets

Outlets

Dampers

Supply air reduced

Motors defective

Motors disconnected

Wrong fan rotation direction

Noises and vibrations

Motor bearings defective

Impellers out of balance

Impellers damaged or worn

Bolts or components loose

Fan operates in stall condition, 
which may lead to damage.

Aged or ruptured vibration 
dampers

8. Inspection and test

It is recommended to test and inspect the 
fans at regular intervals with regard to 
operability and operation conditions.
Inspect the fans twice a year to ensure 
satisfactory function and long life.

Extent of inspection

Measure power consumption

Verify torques of fixation bolts

Cleaning

inside with pressurised air

outside with a lint-free cloth with 
a mild soapy water solution

Visual inspection

Rotors

Fan casings

Electrical connections

Enter all values and observations in a 
log.

9. Sound

The sound emissions depend on the 
installation and operation conditions, 
hence no general data can be given.

Refer to the fan specifications from the 
AirBox calculation program for specific 
emissions and to the product catalogue 
for more general data.

10. Safety

The installation must be in accordance to 
Novenco

’s, the current and the local 

safety regulations. At a minimum these 
include EN 13850.
It is recommended to review and revise 
safety procedures regularly.

Safety check

Test if safety procedures and the 
installation work correctly.

Check if safety regulations have 
been changed and if the installation 
should be revised.

Consider additional measures to 
improve the safety of the 
installation.

11. Reference documentation

Please refer to the below documents for 
further information about the fans.

Catalogue
Car park jet fans,
standard and hot smoke

Technical specifications

12. Disposal

Dispose of fans suitable for scrapping in 
environmentally safe ways and in 
accordance to current regulations.

The fans and especially the electric 
motors contain a wide range of 
materials, which can all be recycled. 
Make sure worn-out motors and fan 
parts are disassembled and recycled for 
the benefit of the environment.

13. Patents and trademarks

Novenco

®

 and 

 are 

registered trademarks of Novenco 
Marine & Offshore A/S.
ZerAx

®

 is a registered trademark of 

Novenco Building & Industry A/S.

AirBox™ and NovAx™ are trademarks 

of Novenco Building & Industry A/S.

Other trademarks in this document are 
the property of their respective owners.

This document is provided ’as is’. 

Novenco Building & Industry A/S 
reserves the right to changes without 
further notice due to continuous product 
development.
Copyright (c) 2010 - 2021,
Novenco Building & Industry A/S.
All rights are reserved.

14. Quality management

Novenco Building & Industry A/S is 
ISO 9001 and 14001 certified. All fans are 
inspected and tested in the production.

15. Warranty

Novenco Building & Industry A/S 
provides in accordance to the law a 
standard 12 months warranty from the 
product leaves the factory. The warranty 
covers materials and defects from the 
manufacture. Wear parts are outside the 
warranty scope.
Extended warranty can be agreed upon. 
Refer to the contract.

16. Spare parts

Contact Novenco for information about 
and ordering of spare parts.

17. Product lifetime

The fans have a product lifetime of 
20 years. Storage, installation and 
maintenance must be in accordance with 
Novenco

’s instructions, which include 

this installation and maintenance guide.

Содержание NOVENCO CGF

Страница 1: ...Pure competence in air 922646 0 0 NOVENCO JET FANS TYPE CGF INSTALLATION AND MAINTENANCE ENGLISH...

Страница 2: ...d address are on nameplates together with information such as product type and size serial or order number max RPMs weight production year and compliance markings Also on the jet fan casings are namep...

Страница 3: ...nsion bolts with documented load capacity during fire must be installed and loaded as stated in the approval Mount the jet fan to a horizontal plane with a natural frequency at least 20 from the fan r...

Страница 4: ...temperature 5 2 Start procedure Start procedure 1 Start the fan 2 Check for irregular sounds 3 Check after 30 minutes that the fan functions correctly 6 Maintenance The user must always keep the jet...

Страница 5: ...16 1 fig 8 from the fan casing and take it down The arrangement requires twopeople totakedownsafely Make sure topull the motor cable completely free of the fan casing 6 Leave the wire guard affixed to...

Страница 6: ...lation should be revised Consider additional measures to improve the safety of the installation 11 Reference documentation Please refer to the below documents for further information about the fans Ca...

Страница 7: ...ISO 1461 2009 BS DS EN 1886 2007 BS DS EN ISO 5801 2017 BS DS EN ISO 9001 2015 BS DS EN ISO 12100 2010 BS DS EN 12101 3 2015 BS DS EN 12101 6 2005 AC 2006 BS DS EN ISO 12499 2008 BS DSF FprEN ISO 1275...

Страница 8: ...Pure competence in air WWW NOVENCO BUILDING COM...

Отзывы: