background image

1

919044-0

GB

MU 15734 0418

Jet fan types AUO/ARO - ARP/AUZ - AUT/ART - AZT

Installation and maintenance

1. Main components

2. Application

3. Handling

3.1 Marking
3.2 Weights
3.3 Transport

4. Storage

5. Installation

5.1 Before installation
5.2 Installation
5.3 Wiring
5.4 Before service
5.5 Approval for operation
5.6 Start-up procedure

6. Maintenance

6.1 Maintenance
6.2 Precautions before maintenance
6.3 Cleaning
6.4 Vibrations
6.5 Motors
6.6 Dismounting of motors
6.7 Mounting of motor
6.8 Blade pitch adjustment
6.9 Troubleshooting

7. Inspection and test

8. Sound

9. Safety

10. Spare parts

11. Patents and trademarks

12. Quality management

13. Warranty

14. Declaration of conformity

1. Main components

2. Application

The jet fans are standard fans suitable for 
conventional car park ventilation instal-
lations and for smoke control in the 
event of fires.
The fans are unsuitable for use in hazard-
ous environments and must not be used 

in these kinds of environments.

3. Handling

3.1 Marking

The fans are fitted with nameplates with 
manufacturing information such as 
product type, e.g. AUO 380/160-4, serial 
and order numbers, max RPM, weight, 
production year, and CE-marking.
Nameplates on jet fans for smoke control 
include additional data such as air per-

Type

Temperatures

Air

-20 to 55 °C 

Environment -20 to 55 °C

Fire

F200 200 °C for 120 min.
F300 300 °C for 60 min.
F400 400 °C for 120 min.
See specifications on motor plate

Table 1.

 Temperature ranges

AUO

ARO

ARP

Figure 1.

 Main components

Item 01 Inlet cone

Item 07 Fan casing

Item 02 Silencer suction side

Item 08 Silencer pressure side

Item 03 Rotor

Item 09 Deflector / AZT: Outlet cone

Item 04 Motor

Item 10 Suspension brackets / AZT: Base plate

Item 05 Motor suspension and guide vanes

Item 11 Wire guard

Item 06 Start/stop switch or terminal box

Item 12 Centre fairing

AUZ

AUT/ART

AZT

10

07

03

01

04

11

09

05

06

10

08

07

05

04

01

02

03

09

01

12

09

06

10

08

06

04

01

02

03

11

07

09

06

05

11

10

01

05

02

03 04

06 07

08

09

10

01

09

05

02

12

03 04

06 07

08

01 09

10

10

11

06

05

04

11 07

03

Содержание NOVENCO ARO 290

Страница 1: ...Pure competence in air 919044 0 AUO ARO ARP AUZ AUT ART AZT INSTALLATION AND MAINTENANCE ENGLISH ...

Страница 2: ...must not be used in these kinds of environments 3 Handling 3 1 Marking The fans are fitted with nameplates with manufacturing information such as product type e g AUO 380 160 4 serial and order numbers max RPM weight production year and CE marking Nameplateson jetfans forsmokecontrol include additional data such as air per Type Temperatures Air 20 to 55 C Environment 20 to 55 C Fire F200 200 C for...

Страница 3: ...e that these are optional and not part of standard deliveries Arrows on the fans indicate the airflow direction and rotation Within a smoke reservoir the jet fans must be fastened to non flammable ma terials only and must meet current na tional requirements In general the jet fans must be mounted so that there is no risk of them falling down in case of fire If unapproved expansion bolts for high t...

Страница 4: ...s 5 5 Approval for operation The installation must be approved with regard to operation and interaction The person responsible for the operation of the system must initiate this test The approval test must be confirmed The person responsible for the operation of the system must keep the approval testdocuments Forjetfansapprovedfor smoke control the documents must be presented upon request from aut...

Страница 5: ... are disconnected 6 3 Cleaning Cleanfansandsilencerswhenneededby means of pressurised air or vacuum cleaning 6 4 Vibrations Fromthefactory thefansarebalancedto run without vibrations Vibrations occurring during operation are normally an indication of accumula tion of dust and dirt or foreign bodies on the rotor system If ordinary cleaning does not solve the problem the fans must stay off line and ...

Страница 6: ...and that the motor shaft is centred in the fan casing before tightening the set screws item 08 AUZ and AZT Check that the motor shaft is centred in the fan casing before tightening the bolts items 14 3 Mount the rotor item 07 on the motor shaft by means of a jack fastened in the threaded hole of the motor shaft Press the rotor hub to contact against the motor shaft collar Important Do NOT use hamm...

Страница 7: ... and operating conditions hence no general data can be given Refer to the product catalogue and the technical fan specifications 9 Safety The jet fans must be installed according to Novenco s the current and the local safety regulations At a minimum these include EN 13850 It is recommended to review and revise safety procedures regularly Safety check Test if safety procedures and the in stallation...

Страница 8: ...7670 and Denmark no PR 1774428 Granted designs include EU no 001069884 0001 to 001069884 0028 Other trademarks appearing in this document are the property of their respective owners Copyright 1985 2018 Novenco Building Industry A S All rights are reserved 12 Quality management Novenco is ISO 9001 and 14001 certified All fans are inspected and tested before leaving the production 13 Warranty Novenc...

Страница 9: ...Pure competence in air WWW NOVENCO BUILDING COM ...

Отзывы: