Schaffner Group
User and Installation Manual
Output filter FN5420 and RWK5420
48/52
5.3 Step 3: Wiring
5.3.1 Verify safe disconnection of all line side
power
Consult your local safety instructions.
5.3.2 Carefully connect protective earth (PE) wire
to adequate earth potential close to the device
Use a wire diameter of equal or bigger size as fore-
seen for drive/load side power cables – according to
your local codes, drive requirement and safety in-
structions.
Ou
tp
ut
fil
te
r
Dr
iv
e
>150mm
>150mm
>100mm
>100mm
5.3.3 Connect PE wire on the device
with appropriate cable lug to threaded stud according
to torque given in section 3.5.2.
5.3.4 Connect shielding for shielded cables
When using shielded cables, the customer must en-
sure to properly connect the shielding of the cables
between input and output. Proper continuity of
shielding is important for EMC purpose and cannot
be only connected through the PE of the filter/reac-
tor. The customer must ensure that the cable shield-
ing is connected with as much surface as possible to
a wide connector like a bus bar or rail both on the in-
put and output cable. An example shielding connec-
tion system is given in Figure 8 in section 3.5.