ECOsine
®
active Harmonic Filters
– Maintenance Manual for FN3420-200-690-3 23
4.1
Maintenance Schedule
Year after start
operation
Maintenance job
1
2
3
4
5
6
7
8
9
10
11
12
Check operation of main fan, DC-bus
fan and clean fan guards
Check of coolant level
Check coolant pump for any signs of
coolant-leakage
Replace inverter fan (DC bus fan)
Replace pre-charge fuses F1 & F2
Replace 230V auxiliary power supply
fuses F3 & F4
Replace 24V power supply fuses
F45 & F46
Replace cooling system power supply
fuses. F47 & F48
Replace cooling system control unit
fuses F1-F3
Replace air-conditioning fuses
F11
Change cooling liquid
Replace main fan
Table 3: Maintenance schedule 200-690-3