Schaffner Group
User and Installation Manual
Ecosine
max
20/66
2.4 Filter selection table FN 3482/FN 3483 (60 Hz, 3×440 … 480 VAC)
Table 15 FN 3482 filter selection table for models with circuit breaker
Filter
Rated load
power@ 480
V/60 Hz
Motor
drive
input
cur-
rent*
Rated
filter
input
cur-
rent
Typical
power
losses
@ 40°C
Circuit
breake
r rated
cur-
rent
Weight
Ter-
mi-
nal
Fra
me
size
[kW]
[HP]
[Arms]
[Arms]
[W]
[A]
[kg]
[lbs]
FN 3482-350-99-
E0XXSXX
260
350
472
327
2832
200
245
540
Bus-
bar
S10
FN 3482-400-99-
E0XXSXX
300
400
537
375
3200
200
270
595
Bus-
bar
S10
FN 3482-450-99-
E0XXSXX
335
450
595
420
3451
250
295
650
Bus-
bar
S10
FN 3482-500-99-
E0XXSXX
370
500
656
467
3404
250
320
705
Bus-
bar
S12
FN 3482-600-99-
E0XXSXX
450
600
773
563
4173
300
385
849
Bus-
bar
L10
*Motor drive input current without harmonic filter.
Table 16 FN 3482 filter selection table for models with trap disconnect jumper
Filter
Rated load
power@
480 V/60
Hz
Motor
drive
input
cur-
rent*
Rated
filter in-
put cur-
rent
Typical
power
losses
@ 40°C
Weight
Termi-
nal
Frame
size
[kW] [HP]
[Arms]
[Arms]
[W]
[kg]
[lbs]
FN 3482-350-99-
E0XXJXX
260
350
472
327
2832
245
540
Busbar
S10
FN 3482-400-99-
E0XXJXX
300
400
537
375
3200
270
595
Busbar
S10
FN 3482-450-99-
E0XXJXX
335
450
595
420
3451
295
650
Busbar
S10
FN 3482-500-99-
E0XXJXX
370
500
656
467
3404
320
705
Busbar
S12
FN 3482-600-99-
E0XXJXX
450
600
773
563
4173
385
849
Busbar
L10
*Motor drive input current without harmonic filter.