Schaefer IT 1686.4 Скачать руководство пользователя страница 2

77855 Achern-Gamshurst
Oststrasse 17     Germany

Tel. : (49) 78 41 / 20 52-  0

No.

70.IT1686.4 E

Fax : (49) 78 41 / 20 52-52

Rev. A

Page 2/3

Specifications

IT 1686.4

Input

Voltage range
Frequency
Recommended input fuse
No-Load input power
Hold-up time
Immunity:
- ESD
- Fast transients

 

- Surges

220 ... 240V AC -15/+10%, unit switches off at under- and overvoltage
50 / 60Hz
6A slow, external
approx. 20W
10 ms. typical

acc. to EN 61000-4-2 (level 3)
acc. to EN 61000-4-4 (level 3)
acc. to EN 61000-4-5 (level 3)

Output

Waveform
Voltage and current rating 
Power rating
Line regulation
Load regulation (10-90%)
Frequency
Efficiency at full load
Distortion
Overload protection
Surge power 
Short circuit current
Crest factor 
Turn-on rise time
Power factor

sinewave
115V AC
500VA
2 %
3 % typical, 4 % max.
400 Hz, crystal stabilized 
85 % typical
5 % typical 
current limited to approx. 1.05 I

nom

2 x P

nom

  for 1 sec.

electronically limited to 3 x I

nom

approx. 3
Softstart, 100ms typical
cos 

n

 

$

 0.7 inductive / capacitive

General

Temperature coefficient
Operating temperature
Load derating
Storage temperature
Cooling
Switching frequency
Isolation resistance
Isolation test
Safety / Construction 
Earth leakage
RFI-interference
Connection
Mounting instructions

0.05 %/°C typical
-20°C to +75°C
2.5 %/°C from +55°C   
-40°C to +85°C
natural convection
approx. 20 kHz
> 10 M

S

 at 500V DC

acc. to EN 60950-1: 2003
acc. to EN 60950-1: 2003
< 3.5 mA at 230V AC, acc. to EN 60950
acc. to EN 55022, class A
see connection diagram
cooling fins to be vertically arranged /
above and below of inverter at least 40 mm distance to neighboring parts.