background image

5

 

PART#-31600075 LIT-SDD4000-HVAC-S INSTALL REV.A

INSTALLATION PREPARATION

1.  Unpack the components for the installation. Leave the sealing tape on the output tubing 

in the box to keep debris out of the tube.

2.  Chose a mounting point for the SDD4004 unit near (or on) the HVAC duct to be used 

for fragrance. There are two important rules to follow:

 

The system must be mounted below the insertion point for the fragrance tube 
into the duct so that the output tubing runs in a constant positive incline, never 
downward sloping or horizontal.

 

The supplied 6 feet of output tubing can be shortened but not extended, so the 
machine should be mounted within 1.5 m.

3.  Mount the SDD4004 system using the supplied wall bracket and hardware. Make sure 

12V DC power can be brought to the machine.

4.  Locate the point for the duct insertion on the bottom or side of the duct and drill a ¼” 

hole into the duct.

5.  Make a clean cut on one end of the tubing a few inches from the end to unseal it.  

Insert one end of tubing through DUCT MOUNT as shown. (FIG. 4)

6.  Secure the tubing to the Duct Mount as shown using zip ties.  The opening must be just 

past the end of the metal rod and the tubing must be secure to allow the rod and tube 
to be bent if needed to get to a good location inside the duct.

7.  Test fit the duct mount through the hole in the duct. Bend the rod if needed to ensure 

the end of the tube is near the middle of the air flow and the ascending pitch of the 
tube is maintained.

8.  Using 5/16” Drive socket and drill attach Duct Mount to the HVAC duct using the 

provided 12x1 tapping screws. Make sure output tubing does not have any dips or any 
sections that have no incline as this will cause clogging, poor scent performance, and 
possible dripping from the machine.

9.  Cut the free end of the tubing to a 45° angle. This is the side of the tubing that will be 

inserted into the cartridge.

10.  Insert this tubing into the HVAC Cap provided in this kit by twisting and pushing the cap 

onto the tube. The tubing should extend approximately 1” from the end of the cap.

11.  Tighten the HVAC Cap to the cartridge, making sure the cap is on tightly to insure the 

connection will not leak. (FIG. 5)

View From Inside Duct

Содержание ScentDirect HVAC-S

Страница 1: ...rately PARTS INCLUDED 1 PVDF Tubing 6 x OD x 17 ID 30200189 x 6 both ends sealed 2 HVAC Adapter Cap 30400032 3 4x Self Tapping Screws 12x1 30210304 4 Duct Mount Assembly 5 3 Zip Tie 30217001 6 Replace...

Страница 2: ...located Fasten the screw terminal connector to the machine with the screw Part 7 from the kit FIG 1 4 Unlatch and open the door of the SDD4004 system to access the control panel 5 Use the 2 Phillips s...

Страница 3: ...the PCB box through the hole at the rear along with the other wire connectors Feed the wires through the slot in the fan housing FIG 2 11 Pass the wires up and out through the slot shown in the top o...

Страница 4: ...wires are connected to the 2 pins on the control board The 3 pin connector on the control board will be left unused 15 Reattach PCB faceplate assembly to SDD4004 and secure with the 4 flathead screws...

Страница 5: ...ing through DUCT MOUNT as shown FIG 4 6 Secure the tubing to the Duct Mount as shown using zip ties The opening must be just past the end of the metal rod and the tubing must be secure to allow the ro...

Страница 6: ...itch 2 Find a location at least 5 times the diameter downstream from any elbows obstructions fans or any significant change in duct area For a round duct with a 10 diameter the insertion point needs t...

Страница 7: ...together at the connector the red wire on the cable to the side of the connector with the red wire from the machine and tighten securely with a fine slotted screwdriver 9 IMPORTANT Check that the HVA...

Страница 8: ...For further assistance please contact ScentAir Technical Services North America 1 704 504 2320 Europe 33 0 5 62 57 63 20 Asia 852 356 378 42 techservices scentair com...

Отзывы: