14. Taking Into Operation

Attention!

The unit can be damaged by lack of lubricant. To ensure that the compressor is adequately lubricated, the oil, which has 

been displaced during transport, must be allowed to flow back into it. The unit must therefore be allowed to stand for at 

least 30 minutes before being connected to the mains and taken into operation. Upon connection the internal fan will start 

working. If the temperature inside the enclosure is higher than the set value of the controller, both the compressor and 

external air fan start working. Once the air inside the enclosure reaches the set temperature, the compressor and external 

fan will stop.

The unit is pre-set at 95°F, which is suitable for most of the electronic devices.
If Drainage required, use PVC 10mm (3/8 inch) ID Hose.

15. Repair

Failure

Condition

Cause

Solution

Unit Does

Not Cool

Internal fan does not work

Power not connected.

Verify power supply

Internal fan works, external fan 

and compressor do not work

Enclosure temperature is 

below setting temperature (St)

Verify values of parameter "St"

Door switch contact is open

Verify door switch

Controller does not work

Replace controller

Internal fan works, external 

fan and compressor do not 

work Display shows alternating 

"OFF" and temperature

The sequence of the phases 

inside the power supply 

connector is incorrect

Change phases inside power 

supply connector

External and internal fan work, 

compressor does not work

Compressor motor electrical 

failure

Verify external fan, verify 

ambient temperature, clean 

condenser

Capacitor for compressor failed Replace capacitor

Compressor works, external 

fan does not work 

External fan needs to be 

replaced

Replace external fan

Enclosure 

Overheating

Compressor and fans (external 

and internal) work all the time

Unit cooling undersized

Enclosure needs a bigger 

cooling unit

Enclosure needs a bigger 

cooling unit

Thermal compressor protector 

triggered

Verify ambient temperature, 

clean condenser

Refrigerant leakage

Contact dealer/service center

Excessive 

Condensate

Door enclosure open

Ambient air gets into the 

enclosure

Ensure door is closed, add a 

door switch and connect it to 

controller

Door enclosure closed

Enclosure IP degree minimum 

IP54

Seal openings on enclosure

Damaged/misplaced sealing 

strip

Repair strip accordingly

Содержание Enviro-Therm SCE-AC5100B230V

Страница 1: ...unting p 7 8 Mounting Principle p 7 9 Cutout Dimensions p 8 10 Dimensions H x W x D p 8 11 Electrical Connection p 9 12 Controller Programming p 9 13 Wiring Diagram p 13 14 Taking Into Operation p 15 15 Repair p 15 16 Maintenance Cleaning p 16 17 Transport Storage p 16 18 Parts Supplied p 16 19 Warranty Limits of Liability p 17 User Manual SCE AC5100B230V SCE AC5100B230VSS SCE AC5100B230VSS6 ...

Страница 2: ...ctric shock danger Important Safety Instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attention Indicates possible damage to the unit Instruction Indicates possible danger to the environment 2 Legal Regulations Liability The information data and instructions contained in this instruction manual are current at th...

Страница 3: ...ty regulations One can find dangerous voltage above 50V AC or above 100V DC Behind the control cabinet doors On the power supply in the unit housing The units have to be fused according to the type plate and the wiring diagram Switch the unit off immediately if the electric power supply is interrupted Danger Through Incorrect Work on the Unit Only specialized personnel are allowed to maintain and ...

Страница 4: ...oke and evaporator These four components of the refrigerant plant are connected with each other by pipes to form a hermetically sealed system in which the refrigerant R134a circulates 1 Air Intake Cabinet Side 2 Radial Fan Cabinet Side 3 Evaporator 4 Air Outlet Cabinet Side 5 Compressor 6 Air Intake Ambient Side 7 Radial Fan Ambient Side 8 Condenser 9 Air Outlet Ambient Side 10 Filter Dryer 11 Exp...

Страница 5: ... 304 SS6 Stainless Steel AISI 316 Dimensions H x W x D 45 28 x 15 55 x 10 63 inch Weight 109 lbs Cutout Dimensions 12 40 x 10 40 inch 12 40 x 8 30 inch Rated Operating Voltage Frequency 230 V 50 60 Hz Rated Current 95 F 95 F 4 6 A Starting Current 16 A Max Current 7 1 A Power Consumption 95 F 95 F 880 W Max Power Consumption 1 17 kW Fuse Rating 12A T Time Delayed Slow Acting SCCR 5kA Transformer I...

Страница 6: ...y BTU SCE AC5100B230V SCE AC5100B120V SCE AC5100B460V SCE AC5100B230VSS SCE AC5100B120VSS SCE AC5100B460VSS SCE AC5100B230VSS6 SCE AC5100B120VSS6 SCE AC5100B460VSS6 Enclosure Air Temp 131 F 55 C 122 F 50 C 95 F 35 C 68 F 20 C Cooling Capacity Watt Ambient Temperature F 65 75 85 95 105 115 125 135 18 24 29 35 41 46 52 57 8000 7000 6000 5000 4000 3000 2000 2344 2051 1758 1465 1172 879 586 ...

Страница 7: ...stalled at the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the equipment inside the enclosure itself Disconnect power before starting any work inside the enclosure Following this 1 1 Scale Drilling Template drill the holes and make the required cuts on the encl...

Страница 8: ...ack to top 9 Cutout Dimensions 15 55 45 28 10 70 4 SLOPE 312 x10 98 10 83 10 83 10 83 10 83 98 15 55 13 98 12 40 1 57 10 43 59 3 94 8 27 21 06 45 28 MOUNTING PATTERN INTERNAL AIR OUTLET INTERNAL AIR INLET ELECTRICAL CONNECTIONS 10 Dimensions H x W x D ...

Страница 9: ...s closed 12 Controller Programming SET TEST BMS PRG R D 1 2 3 4 The cooling unit is intended to be used as a complementary accessory to larger industrial equipment The unit is used where heat needs to be dissipated from electrical control cabinets or similar enclosures in order to protect heat sensitive components It is not intended for household use The unit has two completely separate air circui...

Страница 10: ...ess Flashes when activation is delayed or inhibited by protection times external disabling or other procedures in progress Flashes when alarms are active Signals operation of unit in heating mode Activated only by manual procedure Setting cooling set point St1 Setting heating set point St2 only for units supplied with internal heater 1 Press SET and display should show St1 and then the pre set val...

Страница 11: ... high temperature alarm threshold default 55 C 131 F 3 Press SET on the desired parameter to display the current value 4 Use or to reach the desired value 5 Pressing SET temporarily saves the new value and returns to the parameters list 6 Repeat steps 2 5 to set other parameters 7 Press PRG for 5 seconds to permanently save the new values Test Function Different test functions can be used dependin...

Страница 12: ... no button is pressed for 10 seconds the display starts flashing and after 1 minute returns to the main display without saving changes l To increase scrolling speed press and hold the or button for at least 5 seconds When pressing PRG for 3 seconds the firmware revision code is displayed for 2 seconds When cleaning the controller panel do not use ethanol hydrocarbons ammonia or their byproducts Us...

Страница 13: ...e Sensor CE Condensate Evaporator CH Compressor Heater C Controller AR Alarm Relay X3 Transformer Connector X4 Electrical Supply Connections 1 L1 230V 2 3 L2 N 230V 4 Earth Ground 5 P1 High Temp alarm NO 6 P2 High Temp alarm COM 7 P3 High Temp alarm NC 8 T1 Door Switch Contact 9 T2 Door Switch Contact Notes 1 Mi1 not used in SCE AC5100B230V SS 2 X6 is plugged into X5 for units with heater 3 Ma1 Ca...

Страница 14: ...B 14 SAGINAW CONTROL ENGINEERING A C USER MANUAL back to top ...

Страница 15: ...ting temperature St Verify values of parameter St Door switch contact is open Verify door switch Controller does not work Replace controller Internal fan works external fan and compressor do not work Display shows alternating OFF and temperature The sequence of the phases inside the power supply connector is incorrect Change phases inside power supply connector External and internal fan work compr...

Страница 16: ...tor with shorted wired positions for door contact Saginaw Control and Engineering 95 Midland Road Saginaw MI 48638 5770 Phone 989 799 6871 Fax 989 799 4524 sce saginawcontrol com 16 Maintenance Cleaning Always switch power supply off before starting any maintenance on the unit Any repairs that may be needed must only be done by qualified personnel The cooling unit is a low maintenance type and for...

Страница 17: ...not exceed minimum and maximum rated temperatures Must not exceed BTU Hr rating Filters must be cleaned regularly Must be installed and grounded in accordance with all relevant electrical and safety codes as well as the National Electric Code and OSHA rules and regulations Must be installed in a stationery application free of vibration Our warranty does not warranty product that has been modified ...

Отзывы: