SAGINAW CONTROL & ENGINEERING  •  A/C USER MANUAL

back to top

7. Mounting

 

Always disconnect the power supply before opening the unit.

Heat load to be dissipated from enclosure should not exceed specific cooling output of the unit at any condition. When 

selecting a cooling unit, always allow for a safety margin of at least 15% extra cooling output in the worst conditions. Air 

inlets and outlets must be completely free from obstruction.

Ensure that flows of air leaving and entering the cooling unit, internal and external, are not obstructed. Cooling unit enclosure 

air suction hole must be installed at the highest possible point. When installing the unit on a door ensure it can take the 

weight.

Before  drilling  the  enclosure,  ensure  the  fixing  elements  and  couplings  will  not  interfere  with  the  equipment  inside  the 

enclosure itself. Disconnect power before starting any work inside the enclosure. Following this 1:1 Scale Drilling Template, 

drill the holes and make the required cuts on the enclosure. This template may have been affected by storage conditions, 

please check this template by verifying values of the largest dimensions before drilling. Fit the sealing strip to the cooling 

unit on the side connected to the enclosure and follow the installation diagram.

8. Mounting Principle

 

1.  M6 Bolts

 

2.  M6 Toothed Washers

 

3.  M6 Flat Washers

 

4. Enclosure

 

5.  Mounting Gasket

 

6.  Cooling Unit

Содержание Enviro-Therm SCE-AC1870B120V

Страница 1: ...nting p 7 8 Mounting Principle p 7 9 Cutout Dimensions p 8 10 Dimensions H x W x D p 8 11 Electrical Connection p 9 12 Controller Programming p 9 13 Wiring Diagram p 13 14 Taking Into Operation p 15 1...

Страница 2: ...tric shock danger Important Safety Instruction Indicates instructions for safe maintenance and operation of the unit Attention Indicates possible burns from hot components Attention Indicates possible...

Страница 3: ...y regulations One can find dangerous voltage above 50V AC or above 100V DC Behind the control cabinet doors On the power supply in the unit housing The units have to be fused according to the type pla...

Страница 4: ...ke and evaporator These four components of the refrigerant plant are connected with each other by pipes to form a hermetically sealed system in which the refrigerant R134a circulates 1 Air Intake Cabi...

Страница 5: ...04 SS6 Stainless Steel AISI 316 Dimensions H x W x D 32 68 x 12 00 x 10 63 inch Weight 71 5 lbs Cutout Dimensions 10 43 x 7 09 inch 10 43 x 6 30 inch Rated Operating Voltage Frequency 120 V 50 60 Hz R...

Страница 6: ...apacity BTU SCE AC1870B230V SCE AC1870B120V SCE AC1870B460V SCE AC1870B230VSS SCE AC1870B120VSS SCE AC1870B460VSS SCE AC1870B230VSS6 SCE AC1870B120VSS6 SCE AC1870B460VSS6 Enclosure Air Temp 131 F 55 C...

Страница 7: ...talled at the highest possible point When installing the unit on a door ensure it can take the weight Before drilling the enclosure ensure the fixing elements and couplings will not interfere with the...

Страница 8: ...ANUAL back to top 9 Cutout Dimensions 32 70 10 70 12 00 4 SLOPE 12 00 32 70 13 80 9 25 7 87 79 98 10 43 1 26 7 09 1 97 6 30 16 09 312 x8 47 MOUNTING PATTERN INTERNAL AIR OUTLET INTERNAL AIR INLET ELEC...

Страница 9: ...closed 12 Controller Programming SET TEST BMS PRG R D 1 2 3 4 The cooling unit is intended to be used as a complementary accessory to larger industrial equipment The unit is used where heat needs to...

Страница 10: ...ss Flashes when activation is delayed or inhibited by protection times external disabling or other procedures in progress Flashes when alarms are active Signals operation of unit in heating mode Activ...

Страница 11: ...high temperature alarm threshold default 55 C 131 F 3 Press SET on the desired parameter to display the current value 4 Use or to reach the desired value 5 Pressing SET temporarily saves the new value...

Страница 12: ...no button is pressed for 10 seconds the display starts flashing and after 1 minute returns to the main display without saving changes l To increase scrolling speed press and hold the or button for at...

Страница 13: ...e Sensor CE Condensate Evaporator CH Compressor Heater C Controller AR Alarm Relay X3 Transformer Connector X4 Electrical Supply Connections 1 L1 120V 2 3 L2 N 120V 4 Earth Ground 5 P1 High Temp alarm...

Страница 14: ...B 14 SAGINAW CONTROL ENGINEERING A C USER MANUAL back to top...

Страница 15: ...ing temperature St Verify values of parameter St Door switch contact is open Verify door switch Controller does not work Replace controller Internal fan works external fan and compressor do not work D...

Страница 16: ...r with shorted wired positions for door contact Saginaw Control and Engineering 95 Midland Road Saginaw MI 48638 5770 Phone 989 799 6871 Fax 989 799 4524 sce saginawcontrol com 16 Maintenance Cleaning...

Страница 17: ...ot exceed minimum and maximum rated temperatures Must not exceed BTU Hr rating Filters must be cleaned regularly Must be installed and grounded in accordance with all relevant electrical and safety co...

Отзывы: