4 Layout and Interfaces
43
innovators for industry
The data channels CHAN1 and CHAN2 transmit
control values to the scan head. The SYNC and CLOCK
channels transmit synchronization and clock signals
to the scan system. The STATUS channel (and, if
appropriate, the STATUS1 channel) receives XY2-100
compliant status signals returned by the scan system.
If very long cables are used for data transmission
between the XY2-100 converter and the scan system,
then the synchronization of bidirectional communi-
cation between the scan system and the RTC
®
5
should be configured. This can be accomplished via
two solder jumpers in the XY2-100 converter. To do
so, carefully open the converter’s housing via its four
clip latches (e.g. using a screwdriver). The solder
jumpers
JP1
and
JP2
are on the converter’s PCB,
between the two D-SUB connectors.
shows
the positions of the jumpers on the PCB. The table
below lists the possible jumper settings and the
corresponding cable lengths. Other jumper settings
as well as cable lengths above 25 m are not recom-
mended.
7
(13) DO NOT CONNECT
(12) DO NOT CONNECT
(11) DO NOT CONNECT
(10) DO NOT CONNECT
(9)
DO NOT CONNECT
(8)
STATUS1 – *
(7)
DO NOT CONNECT
(6)
STATUS – *
(5)
DO NOT CONNECT
(4)
CHAN2 –
(3)
CHAN1 –
(2)
SYNC –
(1)
CLOCK –
DO NOT CONNECT (25)
DO NOT CONNECT (24)
DO NOT CONNECT (23)
DO NOT CONNECT (22)
* (21)
DO NOT CONNECT (20)
* (19)
DO NOT CONNECT (18)
CHAN2+ (17)
CHAN1+ (16)
SYNC+ (15)
CLOCK+ (14)
Pin-out of the XY2-100 converter’s 25-pin female D-SUB
connector
* For i
DRIVE
®
scan systems (intelli
SCAN
®
, intelli
SCAN
de
®
,
intelli
DRILL
®
, intelli
cube
®
, intelli
WELD
®
, vario
SCAN
de
), the
STATUS± channel is the status channel of axis 2 (X axis; this
channel is then also called STATUS2±) and the STATUS1± channel
is the status channel of axis 1 (Y axis). For other scan systems, the
STATUS1± channel can not be used: “DO NOT CONNECT”.
Jumper
Cable length *
JP1 closed
(default
configuration)
0 m to 20 m
JP2 closed
20 m to 40 m
8
JP2
JP1
Positions of solder jumpers
JP1
and
JP2
on the PCB of the XY2-100
converter
JP2
JP1
JP2
JP1
* For each jumper configuration, the recommended cable length
range depends – among others – on the used cable type and can
differ from the values listed above.