14
A S S E M B LY
4 x
allen screws
M6x70
A
A
Fitting the stove onto the plinth
There are two plinths for the Scan
58
. You can see how to fit these
below. Use the key supplied with the service pack to make the atta-
chment secure.
A
Scan
58
with pedestal plinth
If you have decided to connect external combustion air via the pede-
stal plinth, mount the connection piece supplied before fitting the
plinth to the stove.
Scan
58
with "see through" plinth
Fresh air intake
In a well-insulated house, the air used up by the burning process
has to be replaced. This particularly applies to houses with mecha-
nical ventilation. There are different ways of making sure that an air
exchange takes place. The most important thing is to ensure that
there is a supply of air to the room where the wood stove is located.
The external wall vent must be located as close to the wood stove as
possible, and you must be able to close it when you are not using the
wood stove.
National and local building regulations must be followed with
regard to the connection of fresh-air intake.
Closed combustion system
If you have decided to use the stove’s closed combustion system, con-
nect the external combustion air using a ventilation pipe passing
through the wall or floor.
It must not be possible to shut off the ventilation pipe with a valve
•
Minimum Ø100 mm ventilation pipe, maximum length: 6 m
with a maximum of one bend
The Scan
58
with pedestal plinth
External combustion air can be connected via the pedestal or plinth
base by fitting the connection piece supplied to the pedestal plinth
and connecting outdoor air.
External combus-
tion air via wall
External combus-
tion air via floor