Programmable S81-HS system Installation and user manual
Page 1
of 3
S81-F7009-1
Description
Control card for addressable devices using XP95/Discovery Apollo protocol. This card can
control up to a maximum of 127 fire detection devices including : smoke, heat, combined
detectors, alarm buttons, control modules, visual and audible alarm devices.
Technical features
Redundancy:
No
Number of devices per loop
127
Loop maximum current
400mA
Supply voltage:
22-29Vdc
Quiescent current:
90mA
Operating temperature:
-5 / +50 °C
Storage temperature:
-30 / +80 °C
Maximum humidity:
95% (RH) non condensing
Hot swap capability:
yes
Status Indications
The front panel includes 8 LEDs with the following functions:
LED
Indication
Active
Steady on if an input is under alarmed/activated condition
Disabled
Steady on if an input or an output is disabled
Fault
Flashing in case of Fault condition
Loop Fault
Flashing in case of loop short circuit or open loop
Log on Fault
Flashing in case of difference between the detected devices and the programmed ones.
Service
Flashing in case of in case of smoke detectors with dirty lenses
TX Pol.
It lights up every time data are transmitted from the module to loop devices.
RX Pol.
It lights up every time data from loop devices are received
Configuration
By using the configuration program ProS81, the following parameters can be set for each point of the single
devices, according to the relevant type:
Parameter
Type
Mode
Operating mode
Sensors
Latching-NO, Latching-NC, Non-Latching-NO, Non-Latching-
NC
Sensitivity
Sensors
5 sensitivity levels to be selected
Type of indication
Sensors
Fire, Supervisory, Gas, Trouble, Hidden, Buzzer Only
Automatic alarm reset
Sensors
Yes/No
Operating mode
Actuators
Continuous-Normally Energised, Continuous-Normally De-
energised, Intermittent, Pulsing
Timing
Actuators
1 to 15 seconds (only for pulsing and intermittent modes)
Output type
Actuators
Normal / Sounder
Sounder tone
Actuators
15 selectable tones
Sounder volume
Actuators
7 selectable volume levels
Polling LED
Sensors/Actuators Enable/Disable LED lighting up during polling
Enable/Disable status export to
Hosts
Sensors/Actuators No, TCP1, TCP2, RS232
Enable/Disable commands
from Hosts on the channel
Sensors/Actuators No, TCP1, TCP2, RS232