66/90
User manual SCAIME:
NU-Soft-eNod4F-E-0716_235704-C.doc
13.2.8
Set points functioning
The following table describes the possible assignments.
bits
meaning
note
b0
set point 1 commutation mode
0
window
only if output 1 assigned to the ‘set
point’ function
1
hysteresis
b2 b1
set point 1 comparison measurement
00
gross
01
net
10
Sensor input control result
b3
reserved (0)
b4
set point 2 commutation mode
0
window
only if output 2 assigned to the ‘set
point’ function
1
hysteresis
b6 b5
set point 2 comparison measurement
00
gross
01
net
10
Sensor input control result
b7
reserved (0)
b8
(or b0 in CANopen®)
set point 3 commutation mode
0
window
only if output 3 assigned to the ‘set
point’ function
1
hysteresis
b10 b9
(or b2 b1 in CANopen®)
set point 3 comparison measurement
00
gross
01
net
10
Sensor input control result
b11
(or b3 in CANopen®)
reserved (0)
b12
(or b4 in CANopen®)
set point 4 commutation mode
0
window
only if output 4 assigned to the ‘set
point’ function
1
hysteresis
b14 b13
(or b6 b5 in CANopen®)
set point 4 comparison measurement