Page | 2
QUICK REFERENCE GUIDE
Cell Type
Flooded Pocket Plate
Valve Regulated
Flooded Fibre Plate
Plate
SBS Series
KPH,
KPM,
KPL,
VRPP,
KGL,
KGM
KFL,
KFM,
KFH,
KBH,
KBM,
KBL
KFX
Electrolyte SG
1.20
0.01
1.19
0.01
1.22
0.01
Charging Option A*
*Note:
72hr boost charge required every 3-6 months. In addition boost system for 72hrs when any cells voltage falls below 1.36 volts.
Float Charge:
1.40-1.42 Vpc
1.40-1.42 Vpc
1.40-1.42 Vpc
Boost
Charging:
1.54-1.69
Vpc
1.45
Vpc
1.52-1.57
Vpc
Charging Option B**
**Note:
Boost system for 72hrs when any cells voltage falls below 1.36 volts. Use Option A Boost charging voltage data.
Float Voltage Range:
1.46-1.49 Vpc
Not Recommended
1.45 / 1.50 Vpc
Charging Current Limit
.2C
5
= 20% of C
5
.1C
5
= 10% of C
5
.2C5=20% of C
5
Torque Values for SBS Ni-Cd Batteries
Bolt Diameter
Recommended Torque
M5
66 in-lbs (7.5 Nm)
M8
177 in-lbs (20 Nm)
M10
265 in-lbs (30 Nm)
If you have ANY questions or concerns contact SBS Stationary Technical Support.
Early detection and corrections of problems will prevent permanent damage to your battery system!
E-mail:
Phone:
1-800-554-2243