SPECIFICATIONS OF CONTROLLER
Power supply, power
consumption, and current
consumption
See PCD7.LRxx-P5
Room Controllers – Installation & Com-
missioning Instructions (PP31-406)
Ambient temperatur
See picture 0G.
Storage temperature
See picture 0B.
Humidity
5 … 95 % r.h. non-condensing
Dimensions
See pictures 0C, 0E.
Degree of protectio
IP20
IP30 (when mounted with accessory
IRM-RSC or
IRM-RLC)
RECOMMENDATIONS AND RULES
►
Rules regarding electrostatic discharge should be followed.
► If the device is modified in any way, except by the manu
-
facturer, all warranties concerning operation and safety are
invalidated.
►
Make sure that the local standards and regulations are
observed at all times. Examples of such regulations are VDE
0800 and VDE 0100 or EN 60204-1 for earth grounding.
►
Use only accessory equipment which comes from or has been
approved by Honeywell.
►
It is recommended that the device be kept at room temper-
ature for at least 24 hours before applying power. This is to
allow any condensation resulting from low shipping / storage
temperatures to evaporate.
►
The device must be installed in a manner (e.g., in a lockable
cabinet) ensuring that uncertified persons have no access to
the terminals.
►
Do not open the device, as it contains no user-serviceable
parts inside!
►
The device is suitable for mounting in fuse boxes conforming
to standard DIN 43880, and having a slot height of max.
45
mm.
►
The device is suitable for panel rail mounting on 35
mm
standard panel rail (both horizontal and vertical rail mounting
possible) – see pictures 0G and 0H.
STANDARDS, APPROVALS, ETC.
PURPOSE OF CONTROL: OPERATING CONTROL and
multifunctional non-safety control intended for HVAC in home
(residential, commercial, and light-industrial) environments
■
24
V models:
UL 60730-1, Standard for Automatic Electric Controls for
Household and Similar Use, Part 1: General Requirements
■
CE-approved
■
FCC part 15B-compliant.
CONSTRUCTION OF CONTROL: Independently mounted
electronic control unit with fixed wiring. Panel-mounted on a
DIN rail.
SHOCK PROTECTION: Class II.
POLLUTION DEGREE: 2.
RATED IMPULSE VOLTAGE:
■
230
V circuits: 2500
V
■
24
V circuits: 500
V
NOTE:
Keep AC mains supply/load cables separate from
signal wiring!
RELAY SPECIFICATIONS
CAUTION
RISK OF ELECTRICAL SHOCK OR EQUIPMENT DAMAGES!
It is not permitted to combine low voltage and line voltage in
the relay block.