Technical data S-Bus
Bus system
S-Bus
Transmission rate
4800-9600-19 200-38 400-57 600-115 200.
The transmission Baud rate is automatically detected
Transmission mode
Data
Bus length (max.)
1200 m (without repeater)
Response time:
Write: 60 ms
Read: 60 ms
■
The interface works only if the phase 1 is connected.
■
The communication is ready 30 s after the power on.
■
The use of energy meter in Bus with intensive communication could reduce the performance of the Bus
■
Refresh time for the data is 10 s. For this reason one energy meter should be not polled faster as 10 s.
■
254 devices could be connected to the S-Bus. Over 128 devices, a repeater should be used.
■
The interface don’t have a terminal resistor, this should be provided external.
■
For a description of the used registers please look at the register page
Data transmission
■
Only «read/write» register instructions are recognized.
■
Only one register can be written at a time.
■
The device will respond „NAK“ if more than 1 register is written.
■
Up to 10 Registers could be read at a time.
■
The device will respond „NAK“ if more than 10 registers are read.
■
The device will not respond to any unknown query.
■
The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM
(transmission rate» etc.)
Change the S-Bus address direct on device
■
To modify the S-Bus address, press 3 sec on
►
touch
■
In menu,
▼
increase address by 10,
►
increase by 1
■
Once the address is selected wait for the root menu to come back