SBC Saia PCD ALD1D5FD Скачать руководство пользователя страница 10

Register

For double registers (4 – 5, 16 – 17, 28 – 29, 30 – 31) the high register is sent first (big-Endian). 

Partial counter (30 – 31) can be reset by writing 0 in both registers in the same message. 

R

Read

Write Description

Unit

1

X

Firmware-Version

Ex: 11 = FW 1.1

2

X

Number of supported registers

Will give 40

3

X

Number of supported flags

Will give 0

4–5

X

Baudrate 

Ex: Baudrate High = 1    Baudrate Low = 49664

      1 × 65536 + 49664 = 115 200 bps

6

X

Not Used

Will give 0

7

X

Type / ASN function

Will give «AL»

8

X

Type / ASN function

Will give «D1»

9

X

Type / ASN function

Will give «D5»

10

X

Type / ASN function

Will give «FD»

11

X

Type / ASN function

Will give «00»

12

X

Type / ASN function

Will give «Ax»

x : 2 = Non MID

x : 3 = MID

13

X

Type / ASN function

Will give «A4»

14

X

Type / ASN function

Will give «4»

15

X

HW vers. Modif.

Ex: 11 = HW 1.1

16–17

X

Serial number

Unique 32 bit serial number Low

18

X

Serial number

Unique 32 bit serial number High

19

X

Not Used

Will give 0

20

X

Not Used

Will give 0

21

X

Not Used

Will give 0

22

X

Status

0 = no Problem

1 = problem with last communication request

23

X

Response Timeout

ms

24

X

X

1)

Modbus Address

Range 1–247

25

X

Error register

0 : No error      1 : Error 

26

X

Not Used

Will give 0

27

X

Not Used

Will give 0

28–29

X

WT1 total

Counter Energy Total Tariff 1 

10 

–2

 kWh (multiplier 0,01)

Ex: WT1 total High = 13   WT1 total Low = 60383    

      13 × 65536 + 60383 = 912351 = 9123.51 kWh

30–31

X

X

WT1 partial

Counter Energy Partial Tariff 1

10 

–2

 kWh (multiplier 0,01)

Ex: WT1 partial High = 13   WT1 partial Low = 60383

      13 × 65536 + 60383 = 912351 = 9123.51 kWh

32

X

Not Used

Will give 0

33

X

Not Used

Will give 0

34

X

Not Used

Will give 0

35

X

Not Used

Will give 0

36

X

URMS phase 1

Effective Voltage of Phase 1

V

Ex: 230 = 230 V

37

X

IRMS phase 1

Effective Current of Phase 1

10 

–1

 A (multiplier 0,1)

Ex: 314 = 31.4 A

38

X

PRMS phase 1

Effective active Power of Phase 1

10 

–2

 kW (multiplier 0,01)

Ex: 1545 = 15,45 kW

39

X

QRMS phase 1

Effective reactive Power of Phase 1

10 

–2

 kvar (multiplier 0,01)

Ex: 1545 = 15,45 kvar

40

X

cos phi phase 1

10 

–2

 (multiplier 0,01)

Ex: 67 = 0,67

1)

 The Modbus Address register is not writable with a broadcast message.

Содержание Saia PCD ALD1D5FD

Страница 1: ...nung I A Zeigt den Strom 2000 Imp kWh Pulsiert entsprechend der bezogenen Leistung Bei Fehler Anschl sse 1L 2L vertauscht pulsiert das Segment mit 600 600 ms Hinweise vor dem Anschliessen Um Feuchtigk...

Страница 2: ...lusswiderstand dieser sollte extern bereitgestellt werden Die verwendeten Register sind in der Registerliste beschrieben Daten bertragung Nur Read Holding Registers 03 Write Multiple Registers 16 Anwe...

Страница 3: ...2 5mm2 Control circuit screwdriver pozi no 0 slot no 1 torque 0 5 Nm Operating 25 55 C noncondensing temperature according standard EN50470 Environment Mechanical M2 Electromagnetic E2 Notes before c...

Страница 4: ...erminal resistor this must be provided external For a description of the used registers please look at the register page Data transmission Only Read Holding Registers 03 Write Multiple Registers 16 in...

Страница 5: ...U V Indica la tensione I A Indica la corrente 2000 impulsi kWh Impulsi secondo l uscita indicata Indicazione dell errore inver sione connessioni 1L 2L pulsa di tempo di cyclo 600 600 ms Dichiarazione...

Страница 6: ...be essere disponibile esternamente Per una descrizione dei registri utilizzati consultare la Pagina Registri Trasmissione dei dati Vengono riconosciute solo le istruzioni Read Holding Registers 03 Wri...

Страница 7: ...mmation totale T part kWh Consommation partielle Peut tre remis z ro P kW Puissance instantan e U V Tension I A Courant 2000 pulses kWh Impulsions en fonction de la puis sance absorb e Indication d er...

Страница 8: ...d une r sistance de terminaison celle ci doit tre mise en place de fa on externe Les registres utilis s sont d crits dans la liste de registres Transfert de donn es Seules les instructions Read Holdin...

Страница 9: ...Pic 3 Pic 2 Pic 4 B U V P P P kW kW kW I A 2000 Imp kWh T part kWh T total kWh ALD1D5F 5560 L1 N B U V P P P kW kW kW I A 2000 Imp kWh T part kWh T total kWh ALD1D5F D D Modbus pair of wires twisted m...

Страница 10: ...give 0 21 X Not Used Will give 0 22 X Status 0 no Problem 1 problem with last communication request 23 X Response Timeout ms 24 X X1 Modbus Address Range 1 247 25 X Error register 0 No error 1 Error...

Страница 11: ...Menu to display the value on LCD Start T total Total consumption Tpart Partial consumption P Instantaneous power 3 s 3 s...

Страница 12: ...ed heat and power station protocol VISI energy lift cooling heating ventilation temperature setpoint lighting shade control sanitation sheduler VISI trending remote alarming VISI visualization VISI bu...