Wiring the terminal block for the supply voltage
Installation
3.3
Wiring the terminal block for the supply voltage and the grounding
WARNING
ELECTRIC SHOCK
Connect only a supply voltage that corresponds to the type plate of your device.
Never insert sharp objects (small screwdrivers, wires, etc.) into the connection terminals
for the supply voltage, and do not touch the terminals.
Failure to follow these instructions can result in death, serious injury, or equipment dam-
age.
A 3-pin terminal block is used for the grounding and for connecting the supply
voltage.
The supply voltage is only connected with the ground connection via protective
elements.
The shielding ground of the connectable twisted pair cables is connected to the
ground connection as a conductor.
24 V
0 V
Figure 1: 3-pin, pluggable terminal block for power supply and grounding
Type of the voltages
that can be connected
Specification of the supply voltage
Connections
Gleichspannung
Nennspannungsbereich DC
12 V ... 24 V
Spannungsbereich DC
inklusive maximaler Toleranzen
9,6 V ... 32 V
24 V Pluspol der
Versorgungsspannung
0 V Minuspol der
Versorgungsspannung
Funktions-
erdeanschluss
Table 2:
Type and specification of the supply voltage and pin assignment on the device
Proceed as follows:
■ Ensure the required conditions for connecting the supply voltage.
See „Requirements for connecting the supply voltage“ auf Seite 1-3.
■ Pull the terminal block off the device.
■ Connect the ground connection.
■ Connect the power supply cables.
■ Plug the terminal block into the connection on the housing.