background image

WALL

INSTALLATION INSTRUCTIONS   

|

   31-00133  

  PCD7.LR-TR4x Wall Modules   

|

   

3

Fig. 5.  Options for Wiring Multiple PCD7.LR-TR4x

Fig. 6. Terminal connections.

Each wall module on a Sylk bus must use a different bus address, 
and there may be multiple PCD7.LR-TR4x wired on a single Sylk 
bus. To change the bus address of a wall module, adjust the 
address dipswitches to match that of the desired bus address 
(1-15). Use the bus address label, shown in Fig. 7, as a reference. 
The default address for both PCD7.LR-TR40 and PCD7.LR-TR42 is 1. 
The address on the wall module must match the address in the 
configuration tool. 

Setting the Wall Module Bus Address Dial

Fig. 7. Bus address settings label.

When all wiring is complete, hook the top side, and then snap 
down like on a hinge. See Fig. 8. 

Attaching the Wall Module to the Subbase

To remove the wall module from its subbase:

1. Locate the two snaps on the bottom of the IFC .
2. Push a screwdriver into each snap to release the IFC 

from the subbase. 

3. Pull the wall module up and away from the subbase. 

See Fig. 8.

Removing the Wall Module from Subbase

Fig. 8. Drilling template (view from above)

TO CONTROLLER

TWO WIRES INTO ONE TERMINAL

DAISY-CHAINING 

MULTIPLE PCD7.LR-TR4x

TO CONTROLLER

TO PCD7.LR-TR4x

13 mm

STRIP 13 mm 

FROM WIRES 

TO BE ATTACHED 

AT ONE TERMINAL.

1.

2.

TWIST WIRES

TOGETHER

WITH PLIERS

(A MINIMUM OF

THREE TURNS).

3.

CUT TWISTED END OF WIRES TO 

5 MM BEFORE INSERTING INTO 

TERMINAL AND TIGHTENING

SCREW. THEN PULL ON EACH WIRE

IN ALL TERMINALS TO CHECK FOR

GOOD MECHANICAL CONNECTION.

WALL MODULE

TERMINALS

HOME RUNNING 

MULTIPLE PCD7.LR-TR4x 

Содержание PCD7.LR-TR42

Страница 1: ...outlet box see Fig 3 When mounting directly on a wall use the type of screws appropriate for the wall material CAUTION Erratic System Operation Hazard Failure to follow proper wiring practices can intro duce disruptive electrical interference noise Keep wiring at least one foot away from large inductive loads such as motors line starters lighting ballasts and large power distribu tion panels Shiel...

Страница 2: ... ballasts etc Shielded cable recommended only if there is a need to reduce the effect of electrical noise d These distances also apply for shielded twisted pair All terminal connections can be made to the backside of the module There are no field adjustable replaceable components inside the module Attach the wires from the programmable controller and network to the appropriate wall module terminal...

Страница 3: ...ring is complete hook the top side and then snap down like on a hinge See Fig 8 Attaching the Wall Module to the Subbase To remove the wall module from its subbase 1 Locate the two snaps on the bottom of the IFC 2 Push a screwdriver into each snap to release the IFC from the subbase 3 Pull the wall module up and away from the subbase See Fig 8 Removing the Wall Module from Subbase Fig 8 Drilling t...

Страница 4: ...on t match between the wall module and the PG5 config tool POWER UP Fig 9 PCD7 LR TR42 Wall Module LCD display startup screen 1 Fig 10 PCD7 LR TR42 Wall Module LCD display startup screen 2 Fig 11 PCD7 LR TR42 Wall Module LCD display startup screen 3 For PCD7 LRxx and RoomUp users the user interface and parame ters are downloaded automatically from the RoomUp tool Refere also to the PCD7 LRxx INSTA...

Отзывы: