INSTALLATION INSTRUCTIONS   

|

   31-00133

PCD7.LR-TR40 and PCD7.LR-TR42 

LCD and non-LCD Wall Modules

BEFORE INSTALLATION

Fig. 1.  PCD7.LR-TR42

Mount the wall module on an inside wall approximately 1372 mm 
from the floor (or in the specified location), to allow exposure to 
the average zone temperature. Do not mount the wall module on 
an outside wall, on a wall containing water  pipes, or near air ducts. 
Avoid locations that are exposed to discharge air from registers or 
radiation from appliances, lights, or the sun.
The wall module can be mounted on a wall, on a standard utility 
conduit box using 3.5 mm screws or on a 60 mm wall outlet box 
(see Fig. 3). When mounting directly on a wall, use the type of 
screws appropriate for the wall material.

  

CAUTION 

Erratic System Operation Hazard.
Failure to follow proper wiring practices can intro-
duce disruptive electrical interference (noise). 

Keep wiring at least one foot away from large inductive loads such 
as motors line starters, lighting ballasts, and large power distribu-
tion panels. 
Shielded cable is required in installations where these guidelines 
cannot be met.
Ground the shield only to the grounded controller case.

IMPORTANT

All wiring must comply with local electrical codes and 
ordinances or as specified on installation wiring dia-
grams.

•  For information on Sylk bus distance limitations,  

see Table 1 on page 2.

•  All wiring is polarity insensitive.

INSTALLATION

Fig. 2. Subbase mounting holes and locking tabs (in mm).

MOUNTING DIMENSIONS 

Содержание PCD7.LR-TR42

Страница 1: ...outlet box see Fig 3 When mounting directly on a wall use the type of screws appropriate for the wall material CAUTION Erratic System Operation Hazard Failure to follow proper wiring practices can intro duce disruptive electrical interference noise Keep wiring at least one foot away from large inductive loads such as motors line starters lighting ballasts and large power distribu tion panels Shiel...

Страница 2: ... ballasts etc Shielded cable recommended only if there is a need to reduce the effect of electrical noise d These distances also apply for shielded twisted pair All terminal connections can be made to the backside of the module There are no field adjustable replaceable components inside the module Attach the wires from the programmable controller and network to the appropriate wall module terminal...

Страница 3: ...ring is complete hook the top side and then snap down like on a hinge See Fig 8 Attaching the Wall Module to the Subbase To remove the wall module from its subbase 1 Locate the two snaps on the bottom of the IFC 2 Push a screwdriver into each snap to release the IFC from the subbase 3 Pull the wall module up and away from the subbase See Fig 8 Removing the Wall Module from Subbase Fig 8 Drilling t...

Страница 4: ...on t match between the wall module and the PG5 config tool POWER UP Fig 9 PCD7 LR TR42 Wall Module LCD display startup screen 1 Fig 10 PCD7 LR TR42 Wall Module LCD display startup screen 2 Fig 11 PCD7 LR TR42 Wall Module LCD display startup screen 3 For PCD7 LRxx and RoomUp users the user interface and parame ters are downloaded automatically from the RoomUp tool Refere also to the PCD7 LRxx INSTA...

Отзывы: