Saia-Burgess Controls AG
User Manual PCD2.M4x60 │
Document 27-648
│ Edition ENG06 │ 2020-10-21
X6 and X7 - Ethernet Switch Port #9
Communication ports
12-5
12
12.5
X6 and X7 - Ethernet Switch Port #9
Do not
remove
M
emor
y
CPU
X2
MPI
X1
X3Ext
X4
0
16
32
48
O C
Error
Run
Halt
X8
X6
X5
X7
Slot A
X9
S1
Bat
t
M1
S2
PCD7FxxxS
M
emor
y
M
emor
y
M
emor
y
PCD2.M4560
PCD7.F7500
X6
X7
`
A 10/100 Mbits switch on X6 and X7 is
used for the Ethernet connection, which
automatically adapts to the two speeds.
`
The two sockets with the same Ethernet
address can be used independently of
each other in terms of speed.
`
Data transfer and programming
or debugging are possible without
restrictions.
X6
X7
Function
2 Port Switch
Socket type
RJ45, metal housing, 2 LEDs
LEDs
yellow
Link and activity
green
Speed
Off = 10 Mbits / On = 100 Mbits
Port #
9
Wiring
Standard Ethernetcabel (f.e. Cat 5e)
un-crossed and crossed is supported.
`
It is advisable to discuss with the network responsible technician whether an
undesired network load might occur. Depending on the application program, a
PCD behaves differently in terms of communication (Trafic) than, for example,
an office computer.
`
In any case, it is recommended to create a separate PLC network.