User Manual PCD2.M4x60 │
Document 27-648
│ Edition ENG06 │ 2020-10-21
X4 - RS-485 (Port #0, not electrically isolated)
Communication ports
12-3
12
12.3
X4 - RS-485 (
Port #
0, not electrically isolated)
In S-Bus, Modbus or MC4 communications mode, an RS-485 link can be
established via port 0 with terminal block X4, terminals 8 and 9.
Do not
remove
M
emor
y
CPU
X2
MPI
X1
X3Ext
X4
0
16
32
48
O C
Error
Run
Halt
X8
X6
X5
X7
Slot A
X9
S1
Bat
t
M1
S2
PCD7FxxxS
M
emor
y
M
emor
y
M
emor
y
PCD2.M4560
PCD7.F7500
S1
X4
9
D
/D
WD
WD
RX - TX
/RX - /TX
8
7
6
5
4
3
2
1
0
S1
O
C
RS 485
Bus-cable
terminal block
X4
Open
Close
Switch S1, connecting or disconnecting the RS-485 termination resistors
`
With switch S1, the terminating resistors are switched on or off. Switch S1 must
be set to “C” (closed) at both outer stations. For all other stations switch S1
remains in the position “O” (factory setting).
Schematic diagram of an RS-485 bus with terminating resistors.
+5 V
/RX - /TX
n
n
39
n
/n
/n
/n
38
RX - TX
+5 V
Pull up
330 Ohm
Termination
Resistor
150 Ohm
Segment length max. 1200 m
max. 32 stations
Bus RS-485
First station
Middle stations
End station
Pull down
330 Ohm
`
For more details see in the Manual “26-740, Installation components for RS-485
Networks”.