background image

Sauter Italia S.p.a. CODE:RDB900F902

RDB900F902

User interfaces, with color touch-screen TFT graphic display

version 2.0

DIMENS.

MINIMUM

TYPICAL

MAXIMUM

A

104.0 (4.094)

104.0 (4.094)

104.8 (4.125)

B

70.0 (2.755)

70.0 (2.755)

70.8 (2.787)

C

22.0 (0.866)

23.0 (0.905)

24.0 (0.944)

D

40.8 (1.606)

41.8 (1.645)

42.8 (1.685)

3.2

Installation

Installation is:
• panel mounting (with optional accessories EPVP01 and 0027000007)

• built-in mounting, in traditional box (like “506” by BTicino)

Fixing screws are always supplied by the builder.

In this example panel mounting, with 4 screws (supplied by the builder).

To the front of the devices can be applied the plates EPVP01 (to order
separately) made of black plastic material.

3.3

Additional information for installation

• working  conditions  (working  temperature,  humidity,  etc.)  must  be

between the limits indicated in the technical data

• do not install the instrument close to heating sources (heaters, hot air

ducts, etc.), devices provided with big magnetos (big speakers, etc.),

locations subject to direct sunlight, rain, humidity, dust, mechanical
vibrations or bumps

• according to the safety legislation, the protection against electrical

parts must be ensured by a correct installation of the instrument; the

parts that ensure the protection must be installed so that you can not
remove them if not by using a tool.

GB

ENGLISH

1

GETTING  STARTED

1.1

Important

Read  these  instructions  carefully  before  installing  and  using  the  instrument  and  follow  all  additional  information  for  installation  and  electrical

connection; keep these instructions close to the instrument for future consultations.

The  instrument  must  be  disposed  accor ding  to  the  local  legislation  about  the  collection  for  electrical  and  electr onic

equipment.

2

INTRODUCTION

2.1

Introduction

The  remote  user  interfaces  belonging  to  the  RDB900F902 series  are  devices  studied  to  allow  operating  (also  at  a  distance)  on  the  configurable
controllers belonging to the RDT900 series.

The user interface of  RDB900F902 is made of a 320 x 240 pixel color touch-screen TFT graphic display and according to the IEC standards guarantees an

index of protection IP40 (IP65 with gasket 0027000007).

They can easily be integrated in residential and commercial rooms; at the front of the interfaces it is possible to apply the p lates EPVP01 or the plates
belonging to the series “Living” and to the series “Light” Bticino.

They can be powered both in alternating and in direct current (12... 24 VAC/12... 30 VDC).

All the models have an alarm buzzer, a real time clock, a CAN port and a USB communication port. 
Installation is by panel, built-in (in box like "506E" BTicino) .

3

SIZE AND INSTALLATION

3.1

Size

Size in mm (in).

4

ELECTRICAL CONNECTION

4.1

Electrical connection

Position micro-switch 1 on position OFF and position micro-switch 2

on position ON to plug in the termination of the CAN port.

Connector 1:

 CAN port.

PIN

MEANING

1

ground

2

signal -

3

Also look at the baud rate of the CAN port of the controller.

Connector 2:

 power supply (12... 24 VAC/12... 30 VDC).

PIN

MEANING

4

power supply

5

power supply

Connector 3:

 DO NOT USE IT

4.2

Additional information for electrical connection

• do not operate on the terminal blocks with elec. or pneumatic screwers

• if the instrument has been moved from a cold location to a warm

one, the humidity could condense on the inside; wait about an hour

before supplying it

• test the working power supply voltage, working electrical frequency

and  working  electrical  power  of  the  instrument;  they  must  corre-
spond with the local power supply

• disconnect the local power supply before servicing the instrument

• connect the device to a CAN network with CANBUS communication

protocol using a shielded twisted pair

• connect the power cables the most possible away from the signal’s

ones

• for repairs and information on the instrument please contact Sauter

sales network.

5

TECHNICAL DATA

5.1

Technical data

Purpose of control:  user interface for configurable controllers.

Construction of control:  independently mounted control.

Operating time:  continuous.
Box:  self-extinguishing transparent.

Size:  118.0 x 111.0 x 26.7 mm (4.645 x 4.370 x 1.051 in).

Size refers to the instrument with the connectors properly plugged.

Installation:

 installation is:

• panel mounting (with accessories)

• built-in mounting, in traditional box (like “506” by BTicino)

Fixing screws are always supplied by the builder.

To the front of the devices can be applied the plates EPVP01 (to order

separately) made of plastic material, available in black

Frontal protection:  IP40 (according to the IEC standards, IP65 for

panel mounting with gasket 0027000007, to order separately); type 1

enclosure for UL and CSA.

Connections:

 extractable male + female terminal blocks (power sup-

ply,  CAN  port;  nominal  cross  section  of  cables  28 - 16 AWG, 

screw  torque  2.2  lb-in),  A-type  USB  connector  (programming port).

The maximum length of the connecting cables of the CAN port de-

pends on the baud rate of the CAN port of the controller:
• 1,000 m (3,280 ft) with baud rate 20,000 baud

• 500 m (1,640 ft) with baud rate 50,000 baud

• 250 m (820 ft) with baud rate 125,000 baud

• 50 m (164 ft) with baud rate 500,000 baud.

Working temperature:

 from 0 to 55 

°

C (32 to 131 

°

F, 10 ... 90% of

relative humidity (without condensate).

Pollution situation:  2 or more.

Power supply:  12 (±10%)... 24 VAC (±15%), 50/60 Hz (±3 Hz), 3 VA

max. or 12... 30 VDC, 2 W max. supplied from a class 2 circuit.
Protect the power supply by one of the following fuses:

• 250 mA-T if the device is powered in alternating current

• 250 mA-T if the device is powered in direct current.

Overvoltage category:

 I.

Real time clock data maintenance in absence of power sup-

ply:  2 days will battery fully charged.

Battery  charge  time:

  2  min  without  interruptions  (the  battery  is

charged by the power supply of the user interface).

Alarm buzzer:

 incorporated.

Display:  320 x 240 pixel color touch-screen TFT graphic display.

Communication ports:

 2 ports:

• 1 non optoisolated CAN port
• 1 non optoisolated USB port.

I

ITALIANO

1

IMPORTANTE

1.1

Importante

Leggere attentamente queste istruzioni prima dell’installazione e prima

dell’uso e seguire tutte le avvertenze per l’installazione e per il collega-

mento elettrico; conservare queste istruzioni con lo strumento per con-
sultazioni future.

Lo  strumento  deve  essere smaltito  secondo  le  normative

locali in merito alla raccolta delle apparecchiature elettriche

ed elettroniche.

2

INTRODUZIONE

2.1

Introduzione

Le interfacce utente remote della serie RDB900 sono dei dispositivi stu-

diati  per  consentire  di  operare  (anche  a  distanza)  sui  controllori

configurabili appartenenti alla serie RDT900.

L'interfaccia utente di RDB900 è composta da un visualizzatore grafico

TFT touch-screen a colori da 320 x 240 pixel e secondo le normative

IEC  garantisce  un  grado  di  protezione  IP40  (IP65  con  guarnizione
0027000007).

Sono facilmente integrabili sia in ambienti residenziali che commerciali;

al frontale delle interfacce è possibile applicare le placche EPVP01 o le

placche appartenenti alla serie "Living" e alla serie "Light" BTicino.
Possono essere alimentate sia in corrente alternata che continua (12...

24 VAC/12... 30 VDC).

Tutti i modelli dispongono di un buzzer di allarme, di un orologio, di

una porta di tipo CAN  (attraverso  la  quale  è  possibile  collegarli  al 
controllore) e di una porta di comunicazione di tipo USB (attraverso la

quale è possibile caricare le pagine grafiche che devono essere realiz-

zate attraverso un apposito tool ).

RDB900F902