background image

RDT724 F002/F022

P100002032 003 A

2/6

C1: Operating for the first time (continued) 

 

step

Scroll until next 
variable to be 
adjusted

Repeat until you see this display:

step

Repeat until basic display:

When the basic display is shown, the procedure for operating 
the device for the first time has been completed.

Note: 

Use 

menu instead of  step to go to the basic display more 

quickly. In this case, not all the parameters, setpoints, etc. are 
called up (also see section B2).

Important:
As soon as the procedure for first-time operation is completed, 
the installation is operational and all the electrical parts are live.

C2: Set the time and date 

If necessary, press 

menu and –  at the same time to go to 

the basic display in the user level.

menu

Scroll until you see 
the time display

,

Change the time

step

Accept the value 
and select date 
display

,

Change the date

step

Accept the value 
and select year 
display

C2: Set the time and date (continued) 

 

,

Change the year

step

Accept the value 
and select 
summertime 
changeover display

,

Change the 
changeover time

step

Accept the value 
and select 
wintertime 
changeover display

,

Change the 
changeover time

step

Accept the value 

Press 

menu and –  at the same time to return to the basic 

display in the user level.

C3: Select and parameterise the application 

Press 

menu and  at the same time to go to the password 

level.

,

Enter password

Note:

The password for the parameterisation level is 102. 

menu

Password is 
accepted. The 
selected application 
is shown

,

Select the 
application

step

Confirm selection of 
the application

D300:Time 

 

13:25 

A110:E1 function 
 

20:Temp.0-10V 

Setpoint     20.0°C
Act. val.    17.3°C

Setpoint     20.0°C
Act. val.    17.3°C

D300:Time 

 

15:52 

D300:Time 

 

16:15 

D301:Day.month 
We    

14.03 

D301:Day.month 
Fr    2

1.09 

D302:Year 

 

2006 

D302:Year 
 

2007 

D303:Summer time 

1.02:Week.month 

D303:Summer time 

5.03:Week.month 

D304:Winter time 

3.09:Week.month 

D304:Winter time 

5.10:Week.month 

Password? 
 

0

Password? 
 

102 

A001:Application 

204:CTR HCE 

A001:Application 

202:CTR HC 

Содержание flexotron 700

Страница 1: ... Installation Instructions enclosed with it please read these instructions on operating it A2 Key SP Switching point abcd Key labelled abcd Factory settings Basic display showing room setpoint and actual room value B Displays and Operating Controls B1 Front view B2 Operating controls menu Load and confirm or save settings Scroll in steps of 100 step Scroll single steps Change values or settings Pr...

Страница 2: ... display C2 Set the time and date continued Change the year step Accept the value and select summertime changeover display Change the changeover time step Accept the value and select wintertime changeover display Change the changeover time step Accept the value Press menu and at the same time to return to the basic display in the user level C3 Select and parameterise the application Press menu and...

Страница 3: ... manual operating level is 101 C5 Manual operation continued menu The password is accepted The first analogue output is shown Change the value step The next analogue output is shown etc Unlock Lock the output 0 Unlock after exiting manual mode the output is regulated according to the control again 1 Lock the output still remains at this value after you exit from manual mode step Release fix next o...

Страница 4: ...y step Display next error that has occurred step etc C8 Error messages continued After the last listed error message you see this display Use menu to delete all previous error entries Use step to go to the next display without deleting the error entries Press menu and at the same time to return to the basic display in the user level C9 Technical data Dimensions W x H x D 160 x 90 x 58 mm Weight ap...

Страница 5: ...o go to the basic display in the user level 2 x menu Show measured value for first assigned analogue input step etc Show measured value for next assigned analogue input step Show value for first assigned analogue output step Show measured value for next assigned analogue output etc step Show status of assigned digital inputs contact open contact closed step Show status of first assigned relay outp...

Страница 6: ...ess menu and at the same time to go to the basic display in the user level menu Scroll until you see the display to select the switching programme step Scroll until the display of the first switching command Adjust the switching time step Accept the value and call up the next switching command Adjust the switching time etc To add a switching command scroll through the switching programme until you...

Отзывы: