background image

If two buttons are operated at the same time, the middle buttons 
take precedence, i.e. if buttons 1 and 2 are operated, only button 2 
is evaluated. 

Position LED on the switching unit 

The ecoUnit241…246 make it possible to activate skylights. 
Depending on the project, it may be required that the light switches 
must be easy to find even when the room is in darkness. 

Depending on the settings for the function parameters, the position 
LEDs for the room operating unit and the switching unit are on or 
off. 

To enable the position LED of switching unit EY-SU306 to light up, 
the terminals must be connected with the same number as on the 
room operating unit (room operating unit 

 switching unit). 

Terminals Position 

LED 

(EY-SU306)

 

 7 

 6 

LED off (hardware-coded, no influence by function 
parameter) 

 6 

 7 

LED lights up if the room operating unit is 
parameterised accordingly 

Presets/default values 

Different functions can be defined during the engineering or 
commissioning phases. 

Analogue values (direct from sensor)

Value corresponds to voltage at terminal 4 (0…10 V)

The digits on the LCD display (1, 2, 3, 4) are used to set the 
parameters and the offset for the temperature display. 

The following presets (default values) are set ex works: 

Analogue value display in °C (direct from sensor)

MFA 40, comm.2: window symbol appears

MFA 41, comm.4: dew-point symbol appears

Position LED of room operating unit and switching unit = active

Fan display = active

Presence display = active

Display offset for temperature = 0

Function parameters, ecoUnit241…246 

Digit Value 

Description 

Range 

Analogue value display (direct from 
sensor) 

(default) Display in °C (measurement range 

0…40 °C) 

0…99.0 

Resolution 0.1 K 

Display in °F (formula: Tf = Tc * 1.8 + 32)  0…99.0 

Resolution 0.5 K 

Value 0…10 V (95 steps), from terminal 4 
(with smoothing of display) 

Display in °C; resolution 0.1 K 

16.0…25.5

Display in °C; resolution 0.5 K 

-9.5…35.5 

Display in °F; resolution 0.5 K 

5.0…99.0 

rh (symbol with digits 1 & 2), no decimal 
point 

5.0…99.0 

% (no decimal point) 

0…100 

Digit Value 

Description 

Range 

ppm (no decimal point) 

0…9999 

Lx (no decimal point) 

0…9999 

No value display or physical units 

MFA 40, comm. 2 

0 (default)  Window symbol 

 1 

Heating 

symbol 

 2 

Cooling 

symbol 

 3 

Note 

symbol 

Hide setpoint correction OFF 

Reduced symbol (moon) 

 6 

Dew-point 

symbol 

MFA 41, comm. 4 

0 (default)  Dew-point symbol 

 1 

Heating 

symbol 

 2 

Cooling 

symbol 

 3 

Note 

symbol 

Hide setpoint correction OFF 

 5 

Window 

symbol 

Position LED for EY-RU and EY-SU; 
fan display; presence display 

0 (default)  LED = on; fan = active; presence = active 

LED = on; fan = active; presence = 
inactive 

LED = on; fan = inactive; presence = 
active 

LED = off; fan = active; presence = active 

LED = off; fan = active; presence = 
inactive 

LED = off; fan = inactive; presence = 
active 

Show function parameters 

When the ecoUnit241…246 units are connected to the power 
supply ('power up'), there are 60 seconds available to call up 
parameterisation mode. 

When button [D] is pressed for more than 5 seconds during this 
period, the device changes to parameterisation mode. The 
parameterisation is shown. All 4 digits flash (slowly). 

If no button is pressed, the unit changes back to operating mode 
after 5 seconds. 

Adapt function parameters (default values) 

The housing cover of the ecoUnit is located beneath the 
transparent cover or plastic insert. The operating buttons are 
clearly labelled on this surface (A, B, C, D, E, F). 

When the ecoUnit241…246 are connected to the power supply 
('power up'), all the symbols are shown for 1 minute. It is possible 
to change to parameterisation mode during this first minute. 

When button [D] is pressed during this period, the unit changes to 
parameterisation mode. Only digit 4 continues to flash. The 
transition to parameterisation mode is indicated by 'SEt' on the 
display. 

Digit 4 flashes. You can now 'scroll' through the digits from 0 to 9
using buttons [D] and [C].

Press button [C] for a long time to confirm the setting you want.

Digit 4 is continuously lit. This completes the setting of the 
analogue value. Digit 3 is now flashing. 

Содержание EY-RU Series

Страница 1: ...ная 12 мин Класс защиты III EN 60730 1 Функциональные Окружающий класс 3K3 IEC 60721 Уставка дисплея LCD 0 10 V 16 25 5 C CE соответствие через терминал 4 Директива EMC 2004 108 EC EN 61000 6 1 Разрешение 0 1 K EN 61000 6 2 1 Коррекция уставки настраиваемая EN 61000 6 3 Присутствие занятость комнаты 3 режима LCD дисплей EN 61000 6 4 Скорость вентилятора 5 функций LCD дисплей Порт Дополнительная ин...

Страница 2: ...ous labelling inserts are included depending on the device This enables the device to be adapted to room conditions Type Labelling inserts included EY RU241 EY RU244 EY RU246 Engineering notes Fitting ecoUnit241 246 room operating units are suitable for various types of mounting Single mounting 1 device Type of mounting Recessed junction box Accessories Designation scope of delivery Recessed mount...

Страница 3: ...m operating units can be extended by 6 push button functions with the help of the EY SU306 switching unit EYSU306 is fitted with a 2 wire connection to EY RU241 246 and can be used only in conjunction with this device ...

Страница 4: ...be broken open at various points to feed the cable in 0940240701 Fixing plate single 0940240801 Fixing plate double An appropriate fixing plate must be used in conjunction with non Sauter frames e g frames made by manufacturers of light switches The fixing plate is screwed onto a recessed junction box The device insert is placed on the frame and connected to the fixing plate by pressing it in Note...

Страница 5: ...in F resolution 0 5 K 5 0 99 0 5 rh symbol with digits 1 2 no decimal point 5 0 99 0 6 no decimal point 0 100 Digit Value Description Range 7 ppm no decimal point 0 9999 8 Lx no decimal point 0 9999 9 No value display or physical units MFA 40 comm 2 3 0 default Window symbol 1 Heating symbol 2 Cooling symbol 3 Note symbol 4 Hide setpoint correction OFF 5 Reduced symbol moon 6 Dew point symbol MFA ...

Страница 6: ...r the temperature display Values shown on the display On the ecoUnit241 246 if terminal 4 is connected to a 0 10 V signal the display of the ecoUnit s own actual value is overwritten In the 0 10 V range a value is displayed corresponding to the setting of the function parameters see Function parameters for ecoUnit241 246 Setpoint adjuster dXs MFA10 Due to the different ecos types and their differe...

Страница 7: ...рск 391 204 63 61 Курск 4712 77 13 04 Липецк 4742 52 20 81 Магнитогорск 3519 55 03 13 Москва 495 268 04 70 Мурманск 8152 59 64 93 Набережные Челны 8552 20 53 41 Нижний Новгород 831 429 08 12 Новокузнецк 3843 20 46 81 Новосибирск 383 227 86 73 Орел 4862 44 53 42 Оренбург 3532 37 68 04 Пенза 8412 22 31 16 Пермь 342 205 81 47 Ростов на Дону 863 308 18 15 Рязань 4912 46 61 64 Самара 846 206 03 16 Санк...

Отзывы: