EQJW 125: Heating controller
Communication functions
48
7001029003 A
© Fr. Sauter AG
Read and write calendar switching commands via Modbus
The 20 holding registers from 42500 to 42519 contain the 20 possible
calendar switching commands as per the table below:
Command
Date
Numerical
value
(decimal)
1
3
1
1
2
13112
1 = stand-by mode
2 = reduced mode
3 = normal mode
Notes on the weekly and calendar switching programme:
All registers for unused switching commands should contain the numerical
value of 0.
The switching commands should be entered in chronological order (time or
date); the first command of the day or year should, therfore, be
'Command1'.
6.3.2
Modbus data points (coils)
Number of
coil register
Description
Comments
Set
(Coil = 0)
Delete
(Coil = 1)
Coil = 0
means
Coil = 1
means
4
Collective bit
Control of all functions
Yes
No
As
specified
Auton.
57
Bit for terminal 6
Heating medium pump ( see coil
register 96)
Yes
Yes
Off
On
89
Bit for operating
mode
Switch over operating mode
(see holding register 40106)
Yes
No
As
specified
Auton.
90
Bit for final control
element
Control of final control element
(see holding register 40107)
Yes
No
As
specified
Auton.
96
Bit for heating
medium pump
Control of heating medium pump
Yes
No
As
specified
Auton.
116
Bit for setpoint value
TF
Calculation of the setpoint value for
TF
Yes
No
As
specified
Auton.
150
Manual mode
Enable manual mode
Yes
Yes
Inactive
Active
157
Disable modem
Dialling the control station via modem
if a fault occurs is disabled (see
CP23)
Yes
Yes
Inactive
Active
Содержание Equitherm EQJW 125
Страница 1: ......
Страница 2: ...EQJW 125 Heating controller User s Manual 7001029003 A R ...
Страница 7: ...EQJW 125 Heating controller Table of contents 6 7001029003 A Fr Sauter AG ...
Страница 9: ...EQJW 125 Heating controller Symbols used in this manual 8 7001029003 A Fr Sauter AG ...
Страница 11: ...EQJW 125 Heating controller General information 10 7001029003 A Fr Sauter AG ...
Страница 15: ...EQJW 125 Heating controller Description of the controls 14 7001029003 A Fr Sauter AG ...
Страница 20: ...EQJW 125 Heating controller Commissioning 7001029003 A Fr Sauter Ltd 19 ...
Страница 58: ...EQJW 125 Heating controller Economy tips 7001029003 A Fr Sauter Ltd 57 ...
Страница 60: ...EQJW 125 Heating controller Resistance values for the Ni1000 sensors 7001029003 A Fr Sauter Ltd 59 ...
Страница 62: ...EQJW 125 Heating controller Dimension drawing 7001029003 A Fr Sauter Ltd 61 ...