EQJW145: Heating controller
Commissioning
7010015003 A
41
© Fr. Sauter AG
Parameter
Description
Range
Step-
value
CP19
–
Device bus: address of EDB 100 digital room operating unit
auto, 2…32
1
CP20
0
SMS or MOD bus via modem: automatic configuration of modem
0 = not enabled. 1 = enabled
0…1
1
CP21
5
SMS or MOD BUS via modem: dialling pause in minutes
0...255
1
CP22
5
SMS or MOD BUS via modem: timeout in minutes
1…255
1
CP23
5
SMS or MOD bus via modem: number of dialling attempts
1…255
1
CP24
0
SMS or MOD bus via modem: send message even if error is rectified
0 = not enabled. 1 = enabled
0…1
1
CP25
0
SMS via modem: select language for error message
0 = German.
1 = French.
2 = English.
3 = Italian.
4 = Spanish
0…4
1
CP26
0
MOD bus via modem: disable dialling control station in case of fault
0 = not enabled. 1 = enabled
0…1
1
CP27
0
MOD bus via RS485 or MOD bus via modem: control station commands
expire after control station is inactive for 30 minutes
0 = not enabled. 1 = enabled
0…1
1
Tab. 4: Communication parameters
Содержание EQJW145
Страница 1: ...EQJW145 Heating controller Operating manual 7010015003 A R ...
Страница 8: ...EQJW145 Heating controller Symbols used in this manual 8 7010015003 A Fr Sauter AG ...
Страница 10: ...EQJW145 Heating controller General information 10 7010015003 A Fr Sauter AG ...
Страница 46: ...EQJW145 Heating controller Commissioning 46 7010015003 A Fr Sauter AG ...
Страница 78: ...EQJW145 Heating controller Communication functions 78 7010015003 A Fr Sauter AG ...
Страница 82: ...EQJW145 Heating controller Faults 82 7010015003 A Fr Sauter AG ...
Страница 90: ...EQJW145 Heating controller Economy tips 90 7010015003 A Fr Sauter AG ...
Страница 92: ...EQJW145 Heating controller Resistance values for the Ni1000 sensors 92 7010015003 A Fr Sauter AG ...
Страница 94: ...EQJW145 Heating controller Dimension drawing 94 7010015003 A Fr Sauter AG ...
Страница 100: ...EQJW145 Heating controller Technical data 100 7010015003 A Fr Sauter AG ...