Figure 1-16
Supply voltage and load capacity
Figure 1-17
Adjusting the junction box position
6
Position selection 3 x 90°
Tighten
the screw
1.2 Electrical connections
Supply voltage and load of the transmitter according to the
figure 1-16.
We recommend shielded twisted-pair cable as signal
cable.
The signal cable should not be installed near high-voltage
cables, large motors or frequency converters.
The shield of the cable is grounded at the power supply
end or according to the recommendations of the
manufacturer of the used control system.
1. Remove screw
2. Open
Figure1-15
Removing the PLUG
junction box
1
2
Op
en
0.5 ... 1.5 mm
2
Pg9
10044093
10044092
BPLV700AV
2006-12-19
SATRON VG
pressure transmitter
1300354153
10 12
15
20
25
30
35
0
250
500
750
1000
1400
Supply voltage /V
Load /
Ω
40
1250
Operating
region
Min. load using HART® - communication 250
Ω
R
max
= Supply voltage - 12 V
I
max
I
max
= 20.5 mA using HART®-communication
I
max
= 23 mA (when the alarm current 22,5 mA is on)