34 KNX-BIN24
SATEL
Configuration for example shown in
Fig. 17-I
in ETS: Two-channel mode = Yes; Control
scheme = Type A; Number of objects in sequence = 5. Configuration for example shown in
Fig. 17-II
in ETS: Two-channel mode = Yes; Control scheme = Type B; Number of objects in
sequence = 5.
Type of sequence
– you can select the type of sequence (description – see “Sequence”):
binary code
Gray code
queue
queue with pause
queue with fill
Number of objects in sequence
– number of objects whose state can be switched in
sequence (minimum = 2; maximum = 5). Selecting a value higher than 2 will enable the
“FB 1: sequence – Object 3…5” communication objects.
Restart of the module will set to “0” the value of all “FB 1: sequence - Object 1…5”
communication objects.
4.5.6 Counter
It counts events both from the physical channels and from other channels of the module. You
can define in the program (“Two-channel mode” parameter) whether the counter control will
be implemented by using one or two channels. Their current value of the counter is saved to
the “FB 1: counter – Current value” communication object. You can define in the program the