SATEL i-LINK User
Manual Version 1.6
10
3.7.3
Channel selection table
DIP 2 3 4 5
0 0 0 0=disable (channel selection is not in use)
0 0 0 1=ch 1
0 0 1 0=ch 2
0 0 1 1=ch 3
0 1 0 0=ch 4
0 1 0 1=ch 5
0 1 1 0=ch 6
0 1 1 1=ch 7
1 0 0 0=ch 8
1 0 0 1=ch 9
1 0 1 0=ch10
NOTE1!
Check, that both i-LINKs are set to the same channel before turning the power ON.
New channel is activated when the power is turned ON.
NOTE2!
The i-LINK unit will not operate with these settings:
1011, 1100, 1101, 1110 or 1111. The power ON indicator starts to blink in case any of these
settings has been chosen.
ADDRESS/ CHANNEL/
DE-SM
7 DE
Delayed alarm
o
Immediate / Delayed Alarm
In case of a failure in the transmission, the alarm output response can be selected from
immediate alarm to 10 seconds delayed alarm.
8 SM
Safe Mode
o
Unchanged output state / Safe Mode state
In case a failure in transmission, the outputs can be set to remain their status (unchanged)
or change to “Safe Mode” which will switch all outputs to OFF-position. Safe Mode timing
follows the setting of the switch 7 DE, so it can be immediate or delayed by 10 seconds.
Selection table of the Dip–switches 7 and 8
7DE 8SM
0
0 = Immediate Alarm / No Safe Mode
0
1 = Immediate Alarm / Immediate Safe Mode
1
0 = Alarm delayed by 10 seconds / No Safe Mode
1
1 = Alarm delayed by 10 seconds / Safe Mode delayed by 10 seconds
6
Selecting of the transmission standard
According to the European standard for free channel operation, the ratio of the
transmission cycle must not be more than 10/90. This is active when the DIP-switch
number 6 is 0. In position 1 the cycle is faster.
Selection table of the DIP-switch number 6
0= one transmission cycle per second
1= 3 transmission cycles per second.