8.  By putting jumpers on the 

AC FAIL DELAY 

pins, set the time delay after which 230 V AC 

mains  failure will be signaled on the AWS output  (This setting specifies also the AWS 
output restore time). Possible time delay settings: 

 

1800 seconds  – 

 

Pins shorted 

 

10 seconds  – 

 

Pins open 

9.  Using the 

BEEP 

pins, determine, whether the buzzer is to signal troubles (jumper on), or 

not (jumper off). 

In order to avoid the risk of electric shock, put and remove jumpers only 
in deenergized state, i.e. with power supply disconnected. 

10. Connect the batteries according to the color markings. 

The green LED 

 [

BATTERY

] lights up as soon as 230 V power supply is on, however the 

battery charge status will only be known after a full test, i.e. after approx. 12 minutes. The 
battery charge status check is performed every 4 minutes and lasts some ten to twenty 
seconds.  During the tests, the  processor  reduces the power supply voltage to approx. 
21 V, and the loads  are switched over to battery supply.  If the battery  voltage drops to 
approx. 22 V during three consecutive cycles, the APS-524 will report a trouble, and when 
the voltage drops down to 19 V, the APS-524 will disconnect the battery to prevent it from 
being fully discharged and damaged. 
After completion of the test, the LED will remain ON if the APS-524 detects presence of 
a charged battery, or will start blinking if the battery is discharged, or will go out, if there is 
no battery supply.  

Note:  If the battery is not detected after reconnection, the power supply circuit will only 

detect the presence of the battery on the AWB output  when a full test is 
completed (approx. 12 min.). 

The battery test may be optionally disabled  –  to do so, remove the 

BATT. CHECK

 

jumper.  Disabling the  test  will also deactivate the  battery trouble signaling  on the AWB 
output,  however it will not disable the circuit protecting the battery from complete 
discharge. 

11. Switch on 230 V AC power supply (if all connections have been made properly, the LEDs 

  [

MAINS

]  and 

  [

BATTERY

]  should come  on,  while the LEDs 

 [

OVERLOAD

]  and

 

 

[

TEMPERATURE

] should remain off). 

12. Then, you can check the trouble control circuits for proper functioning  (with  BATT. 

CHECK jumper on): 

Disconnect  mains supply

  –  the 

  [

MAINS

]  LED will go out and the APS-524  will start 

audibly signaling the trouble. After the time set on the pins has elapsed, the AWS output 
status will change. After restoring the mains, the LED will come on with steady light, the 
sound will be muted, and – after expiry of the time set on the pins – the AWS output will 
stop signaling trouble. 

Disconnect battery

  –  after approx.  12 minutes the green 

  [

BATTERY

]  LED  will go out 

and the  APS-524  will start audibly signaling the trouble.  The  AWB  output will signal 
emergency condition. Reconnecting the battery will stop the trouble signaling by the LED 
indicator and buzzer after approx. 12 minutes. 

When the APS-524 has been installed and tested for operation, its housing can be closed. 
 

As the APS-524  has no isolating switch to disconnect the mains supply, it is 
important that the user/owner of the device be advised on how it  should be 
disconnected  from the mains (e.g. by indicating the fuse which protects the 
supply circuit). 