16 ACU-270
SATEL
AMD-100
/
AMD-101
– enter the digit 0 (bottom reed switch) or 1 (side reed switch) to
determine which of the two reed switches is to be active.
AMD-102
– for the magnetic contact, enter the digit 0 (bottom reed switch) or 1 (side reed
switch) to determine which of the two reed switches is to be active. For the roller shutter
input, enter 2 digits:
1
st
digit – number of pulses: from 1 to 8.
2
nd
digit – pulse validity: 0 (30 seconds), 1 (120 seconds), 2 (240 seconds) or 3 (unlimited
duration).
AOD-200
– for the first position taken by the detector, enter 3 digits:
1
st
digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum).
2
nd
digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum).
3
rd
digit – sensitivity of dusk sensor: from 1 to 4 (1 – minimum; 4 – maximum).
APMD-150
– enter 3 digits:
1
st
digit – sensitivity of PIR sensor: from 1 to 4 (1 – minimum; 4 – maximum).
2
nd
digit – sensitivity of microwave sensor: from 1 to 8 (1 – minimum; 8 – maximum).
3
rd
digit – the way of operation in the test mode: 0 (alarm triggered after motion is sensed
by both detectors), 1 (alarm triggered after motion is sensed by infrared detector) or 2
(alarm triggered after motion is sensed by microwave detector).
APD-100
– enter 2 digits:
1
st
digit – sensitivity: 1 (low), 2 (medium) or 3 (high),
2
nd
digit – pet immunity option: 0 (disabled) or 1 (enabled).
ARD-100
– enter a number from the 1 to 16 range to determine sensitivity (1 – minimum;
16 – maximum).
ATD-100
– for each position taken by the detector, enter in turn:
letter H (high temperature threshold) or L (low temperature threshold);
numerical value corresponding to a temperature from the -30° C to +70° C range (with
up to 0.5° accuracy),
numerical value corresponding to a tolerance from the 0.5° C to 10° C range (with up to
0.5° accuracy).
AVD-100
– for the magnetic contact, enter the digit 0 (bottom reed switch) or 1 (side reed
switch) to determine which of the two reed switches is to be active. For the vibration
detector, enter 2 digits:
1
st
digit – sensitivity: from 1 to 8 (1 – minimum ; 8 – maximum).
2
nd
digit – number of pulses: from 0 to 7. For the value 0, pulses are not counted.
ASP-100
– enter 2 digits:
1
st
digit – type of acoustic signaling: from 1 to 4.
2
nd
digit – maximum duration of signaling: 1 (1 minute), 2 (3 minutes), 3 (6 minutes) or 4 (9
minutes).
ASP-105
– enter 2 digits:
1
st
digit – type of acoustic signaling: from 1 to 4.
2
nd
digit – maximum duration of acoustic signaling: 1 (1 minute), 2 (3 minutes), 3 (6
minutes) or 4 (9 minutes).
ASP-205
– for both positions taken on the list by the siren, enter 3 digits:
1
st
digit – maximum duration of signaling: 1 (1 minute), 2 (3 minutes), 3 (6 minutes) or 4
(9 minutes).