
8
All current clamps in the kit have built-in protection against clamp connector
disconnection. See the Appendix for a description of the current clamps.
2.7.2 Special Cables
The manufacturer's special cables, together with the standard clamps,
enable the PNA295-1 to perform measurements of
high voltage lines
via
current transformers by measuring the secondary output of the external CT
with 5A nominal secondary current.
NOTE: Using clamp 1000A via the special cable will yield greater
measurement accuracy than using the 120A clamp.
2.7.3 Standard FLEX Current Sensors
The PNA295-1 can work with all standard FLEX current sensors which have
a voltage output signal 1 Volt / 10
q
A, where q = any whole number (see
Appendix B). Maximum measured current is 120% of the nominal current.
The PNA295-1 provides an optional FLEX connector cable for connection to
these current sensors.
Содержание PNA295-1
Страница 1: ...PNA295 1 Portable Network Analyzer Installation and Operation Manual BG0149 Rev B...
Страница 2: ...PNA295 1 Portable Network Analyzer Installation and Operation Manual...
Страница 16: ...11 WIRING DIAGRAMS Figures 2 1 through 2 12 Figure 2 1 PNA295 1 Connections for 3 Wire System Direct Connection...
Страница 17: ...12 Figure 2 2 PNA295 1 Connections for 3 Wire System Direct Connection for THD and Harmonic Measurement...
Страница 18: ...13 Figure 2 3 PNA295 1 Connections for 4 Wire System Direct Connection...
Страница 19: ...14 Figure 2 4 PNA295 1 Connections for 4 Wire Grounded Delta System Direct Connection...