5
2 MODBUS FRAMING
2.1 Transmission Mode
The protocol uses the Modbus Remote Terminal Unit (RTU) transmission mode. In RTU mode,
data is sent in 8-bit binary characters. The 8 bit even parity or 8 bit no parity data format must
be selected when configuring the instrument communications. The data format is shown in the
following table.
Table 2-1 RTU Data Format
Field
No. of bits
Start bit
1
Data bits
c
8
Parity (optional)
1
Stop bit
1
c
Least significant bit first
2.2 The RTU Frame Format
Frame synchronization is maintained in RTU transmission mode by simulating a
synchronization message. The receiving device monitors the elapsed time between receptions
of characters. If three and one-half character times elapse without a new character or
completion of the frame, then the device flushes the frame and assumes that the next byte
received will be an address. The frame format is defined below.
The maximum query and response message length is 256 bytes including check characters.
RTU Message Frame Format
T1 T2 T3
Address Function Data
CRC Check T1 T2 T3
8 bits
8 bits
N * 8 bits
16 bits
2.3 Address Field
The address field contains a user assigned address (1-247) of the instrument that is to receive
a message. Address 0 is used in broadcast mode to transmit to all instruments (broadcast
mode is available only for functions 06 and 16). In this case all instruments receive the
message and take action on the request, but do not issue a response. In the PM130, the
broadcast mode is supported only for register addresses 287-294 and 301-302 (reset energies
and maximum demands), 3404-3415 (reset/clear registers), and 4352-4358 (real-time clock
registers).
2.4 Function Field
The function field contains a function code that tells the instrument what action to perform.
Function codes used in the protocol are shown below in Table 2-2.
Table 2-2 Modbus Function Codes
Code
(decimal)
Meaning in Modbus
Action
03
Read holding registers
Read multiple registers
04
Read input registers
Read multiple registers