Chapter 5 Configuring
T H E P M 1 3 0 P L U S
General
M E T E R S E T U P
88
PM130 PLUS Powermeter Series
Using the Front Display
Select
SEtP
from the main menu to enter the setup menu.
Use the
UP
and
DOWN
arrow buttons to scroll to the required setpoint.
To select a setpoint parameter:
1.
Press the
SELECT
button to activate the middle window.
2.
Use the
UP
and
DOWN
arrow buttons to scroll to the required
parameter.
To change the parameter value:
1.
Press the
SELECT
button to activate the lower window.
2.
Use the
UP
and
DOWN
arrow buttons to select the required value.
3.
Press
ENTER
to confirm the new setting or press
ESC
to discard
changes.
4.
You are returned to the middle window and can configure another
parameter.
To store your new setpoint settings after you configured all setpoint
parameters:
1.
Press the
ENTER
button when the middle window is highlighted.
2.
You are returned to the upper window and can select another
setpoint or exit the menu.
3.
Press
ESC
to exit the menu.
See the table below for the available setpoint options.
Using PAS
Select
General Setup
from the
Meter Setup
menu, and then click on the
Control/Alarm Setpoints
tab.
The following table lists the available setpoint options.
Table 26: Setpoint Options
Display
Label
Option
Range
Description
TriG
Trigger parameter
See Appendix C
The trigger parameter that is used as an
argument in the logical expression
On
Operate limit
The threshold (in primary units) at which the
conditional expression would be evaluated to
true. Not applicable for digital triggers.
OFF
Release limit
The threshold (in primary units) at which the
conditional expression would be evaluated to
false. Defines the hysteresis for analog
triggers. Not applicable for digital triggers.