Appendix G Device Diagnostic Codes
216
EM720 Power Quality and Revenue Meter
Appendix G Device Diagnostic Codes
Diagnostic
Code
Display Message
Description
Reason
2
RAM/Data fault
RAM/Data error
Hardware failure
3
Watchdog reset
Hardware watchdog reset
Hardware failure
4
Sampling fault
DSP/Sampling fault
Hardware failure
5
CPU exception
CPU exception
Hardware failure
6
Run-time error
Run-time error
Hardware failure
7
SW watchdog reset
Software watchdog timeout Hardware failure
8
Power down
Power down
Loss of power
9
Device reset
Warm restart/Device reset
External restart via communications
or by firmware upgrade.
10
Configuration reset
Configuration reset
Corrupted setup data has been
replaced with the default
configuration.
11
RTC fault
RTC fault
The clock time has been lost. With
auto-reset: cleared automatically as
the clock is updated.
12 Configuration
fault
Configuration fault
Factory, calibration or basic device
configuration data has been
corrupted.
13
Low battery
Battery low
Low lithium battery.
With auto-reset.
Battery check or replacement is required.
14
Exp. memory fault
Expanded memory fault
Hardware failure
15
CPU EEPROM fault
CPU EEPROM fault
Hardware failure
18
Coprocessor fault
Coprocessor fault
Hardware failure
20
Library error
C Library error
Hardware failure
22
Task error
Task error
Hardware failure
24
IRIG-B No signal
IRIG-B signal lost
No IRIG-B signal from the GPS
master clock. With auto-reset:
cleared automatically when the
IRIG-B signal is detected.
25
IRIG-B Unlocked
IRIG-B time unlocked
The GPS master clock has lost the
satellite signal. With auto-reset:
cleared automatically when the
satellite signal is locked.
27
Magnet. interference Magnetic interference
Indicates presence of a high
electromagnetic field that can affect
accuracy of energy measurements.
With auto-reset.
29
Motion/tilt sensor
Motion/tilt sensor
The meter has been moved or tilted.
See
for more information on the EM720
built-in diagnostics. See
Device Diagnostics Display
in
Chapter 3 and
how to inspect and clear the device diagnostics in your
meter.
Содержание expertmeter EM720
Страница 1: ...POWER QUALITY AND REVENUE METER EM720 EM720T Operation Manual BG0451 Rev A3 ...
Страница 134: ...Chapter 6 Device Control and Upgrading Operating Event Flags 134 EM720 Power Quality and Revenue Meter ...
Страница 166: ...Chapter 9 Viewing Files and Reports Viewing Waveforms 166 EM720 Power Quality and Revenue Meter ...