Appendix: Technical Specifications
24
Power Supply
3P power supply
(MPS)
Power Supply Inputs from measured AC Voltage inputs
207-480V AC 50/60 Hz
High range power supply (480V option)
96- 575V AC
100-120 V AC 50/60 Hz
Low range power supply (120V option)
45 - 250 V AC
Burden as per IEC 62053-61 multi-function meter
requirements
3 W and <15VA/phase
Battery backup
Power Supply (BPS)
Build-in rechargeable NiMh battery, Redundant
MPS
2.5 hours backup
AUX. Power Supply
(APS)
Low DC Power Supply, Redundant MPS
DC PS module -
Optional
DC input
24V DC ± 15%
Power Consumption
6W maximum
Dielectric insulation withstand
4 KVAC @ 1mn
Terminals for wires size
2 x 4 mm
2
Real Time Clock
Battery backup
According to IEC 61038
Field replaceable Lithium battery
> 3 consecutive years
More than 10 years service
battery life
Input/Output ports
Digital Input
Dry contact - Optically isolated
4 inputs
Wetting (internally) input contact
24 VDC internal power
supply
(5mA wetting current per
contact)
Open contact impedance
> 1M
Ω
Close contact impedance
< 100
Ω
Sampling rate cycle
1ms
Dielectric insulation withstand
4 KVAC @ 1mn
Basic
Terminals for wires size
8 x 2.5 mm
2
Digital Input
Dry contact - Optically isolated
2 inputs
Wetting (internally) input contact
24 VDC internal power
supply
(5mA wetting current per
contact)
Open contact impedance
> 1M
Ω
Close contact impedance
< 100
Ω
Sampling rate cycle
½ cycle (50/60 Hz)
Dielectric insulation withstand
4 KVAC @ 1mn
2DI/2DO module -
Optional
Terminals for wires size
4 x 2.5 mm
2
Solid State outputs
SSR FORM C
2 relays
Maximum switching voltage
250VAC/VDC
Make and carry capacity
0.12A max
Maximum operate time
1 ms
Maximum release time
1 ms
Dielectric insulation withstand
4 KVAC @ 1mn
2DI/2DO module -
Optional
Terminals for wires size
6 x 2.5 mm
2
Relay outputs
Electromechanic FORM C
2 relays
Maximum switching voltage
250VAC/110VDC
Make and carry capacity
10A max
Maximum operate time
7 ms
Maximum release time
5 ms
Dielectric insulation withstand
4 KVAC @ 1mn
2DI/2DO module -
Optional
Terminals for wires size
6 x 2.5 mm
2