SP-MAN-INSTALL-01
Revision 2 21-12-21
9
EOGB
Sapphire
6 - 32kW
Water Content
Litre
62
* Weight (Dry) Heat Exchanger
Kg
46
* Weight (Dry) Overall
Kg
88
Max. Heat output
(Kerosene)
kW
32
Min. Heat output
(Kerosene
)
kW
6
Flow Connection
mm
22
Return Connection
mm
22
Condensate connection
mm
22
Flue diameter
mm
81
Maximum static head
m
7.2
Minimum circulating head
m
0.5
Boiler thermostat range
°C
70
Primary Limit Thermostat (safety shut off temp)
°C
95 +/-3 °C
Secondary Limit Thermostat (safety shut off temp)
°C
110 +/-3 °C
Maximum hearth temperature
°C
100
Electrical supply
Volts
1ph-230-50Hz
Total Consumption
kWh
0.66
Oil connection
Dependant on
installation
Max operating pressure - sealed system
bar
3
* Weight includes burner but excludes flue.
5.0
Technical Boiler information
Heating system pressure (cold)
Calculated depending on system size Refer to the
“Domestic Heating Design Guide”
Operating pressure of pressure relief valve
3 bar
Expansion vessel size
Calculated depending on system size Refer to the
“Domestic Heating Design Guide”
5.1
Technical Boiler information (Sealed System)
Table 1
Table 2
Technical Data