Baud Rate
Configure the transmission rate of connected devices to the transmission rate of the camera.
Transmission Rate Switch 1 Switch 2
2400
OFF
OFF
4800
ON
OFF
9600
OFF
ON
19200
ON
ON
When protocol is set to “PELCO”, set to 2400.
2
Protocol
Select the protocol for controlling the camera.
Protocol
Switch 3
Corresponding Protocol
SSP (SANYO)
OFF
Automatic switching between Sanyo SSP and high speed SSP
PELCO
ON
Automatic switching between PELCO-D and PELCO-P
3
Terminator
When you connect multiple cameras, set the terminator setting (Switch 6) of the final device to “ON” and all other
devices to “OFF”.
When you connect multiple cameras, allocate a unique RS485 protocol address (camera number) to each camera.
Configure the address by setting the dip switches to “ON” and “OFF”.
Configure the switches according to the List of Address Configuration Switches shown below. Circles in the list
indicate “ON”.
When protocol is “SSP (SANYO)”:
Configurable addresses: 1 to 127
Switch 8 is configured to “OFF”.
When protocol is “PELCO”:
Configurable addresses: 1 to 255
To configure the address to a number between 128 and 255, set the switch 8 to “ON”.