background image

293

608

136

12

35

369

345

320

ID:18

5-ID:23.6

900

85

890

18

75

70

113

150

73

70

114

51

70

70

Wide tube service valve

dia.9.52 (3/8") 

× 

2

Narrow tube service valve

dia.6.35  (1/4") 

× 

4

Wide tube service valve

dia.12.70  (1/2") 

× 

2

 

Outdoor Unit 

SAP-CMRV3144EH

Unit: mm

22

Содержание SAP-CMRV1424EH

Страница 1: ...MRV3144EH Capacity 4 0kW 5 6kW 5 6kW 6 8kW 8 0kW Product Code No 1 852 330 12 1 852 336 59 1 852 330 13 1 852 330 14 1 852 330 15 FILE NO REFERENCE NO SM700662 Applicable Indoor Units Wall mounted type For details about the combination refer to Unit Combination Table in the Appendix of this manual SAP KMRV74EH SAP KMRV94EH SAP KMRV124EH SAP KRV184EH SAP KRV244EH NOTE IMPORTANT These air conditione...

Страница 2: ...e fire hazard When Transporting Be careful when picking up and moving the indoor and outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fingers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construc...

Страница 3: ...HOOTING 8 1 Precautions before Performing Inspection or Repair 8 2 Trouble Diagnosis by Error Monitor Lamps 8 3 Checking the Outdoor System 8 4 Trouble Diagnosis of Each Part 8 5 Trouble Diagnosis of Fan Motor 9 REFRIGERANT R410A SPECIAL PRECAUTIONS WHEN SERVICING UNIT 9 1 Characteristics of New Refrigerant R410A 9 2 Checklist before Servicing 9 3 Tools Specifically for R410A 9 4 Tubing Installati...

Страница 4: ...APPENDIX A INSTALLATION INSTRUCTIONS SAP CMRV1424EH APPENDIX B INSTALLATION INSTRUCTIONS SAP CMRV1924EH SAP CMRV1934EH SAP CMRV2444EH SAP CMRV3144EH APPENDIX C UNIT COMBINATION TABLES A 1 A 2 A 3 Page 4 ...

Страница 5: ...SAP CMRV2444EH YES YES YES YES YES SAP CMRV3144EH 2 Room 2 Room 3 Room 4 Room 4 Room YES YES YES YES YES SAP KMRV74EH SAP KMRV94EH SAP KMRV124EH SAP KRV184EH SAP KRV244EH NOTE 1 The table lists the wall mounted type of indoor units as representative models 2 For details on the applicable indoor units other than the wall mounted type refer to the catalog 5 ...

Страница 6: ...GE Maximum Minimum Maximum Minimum 32 C D B 23 C W B 19 C D B 14 C W B 27 C D B 16 C D B 43 C D B 19 C D B 24 C D B 18 C W B _ D B 15 C W B Temperature Indoor Air Intake Temp Outdoor Air Intake Temp Cooling Heating 6 ...

Страница 7: ...W Performance Power Source Max Capacity of Operating Indoor Units kW Auto Hi Me Lo Flare Type A Microprocessor Features 48 47 Electric Expansion Valve Refrigerant Control Refrigerant Amount charged at shipment m Refrigerant Tubing Connections dB A Hi Operation Sound Max allowable tubing length per unit 569 x 790 x 285 Refrigerant Tube Diameter mm 6 35 1 4 x 2 9 52 3 8 x 2 45 0 0 22 Narrow tube Wid...

Страница 8: ...e 4 21 Hi Auto Hi Me Lo Flare Type A Microprocessor Features 52 50 Compressor Locked Rotor Amperes 14 5 0 36 Narrow tube Wide tube mm in mm in Dimensions Weight m3 9 52 3 8 x 2 860 x 1 032 x 413 740 x 900 x 320 Available Voltage Range Running Amperes V Refrigerant Control Operation Sound m Refrigerant Tubing Connections dB A 69 0 Max allowable tubing length per unit 25 Refrigerant Tube Diameter mm...

Страница 9: ...s V 7 70 Compressor Refrigerant Amount charged at shipment g E E R Fan Speeds C O P W W Controls R410A 2 800 mm DC Twin Rotary Inverter Shipping Volume Net Unit Dimensions Package Dimensions Weight Refrigerant Tube Diameter 3 61 W W A Shipping Height x Width x Depth Height x Width x Depth 69 0 Max allowable tubing length per unit 25 3 Room Multi Outdoor Unit 230V 1 198 to 264 19 100 7 3 24 900 Coo...

Страница 10: ...0 g E E R Fan Speeds C O P W W Controls DC Twin Rotary Inverter Shipping Volume Net Unit Dimensions Package Dimensions Weight Refrigerant Tube Diameter Compressor Refrigerant Amount charged at shipment Shipping Height x Width x Depth Height x Width x Depth 69 0 mm 4 Room Multi Outdoor Unit 230V 1 198 to 264 23 200 8 6 29 300 Cooling Heating 1 kg kg 740 x 900 x 320 65 0 V Refrigerant Control mm 6 3...

Страница 11: ... g E E R Fan Speeds C O P W W Controls DC Twin Rotary Inverter Shipping Volume Net Unit Dimensions Package Dimensions Weight Refrigerant Tube Diameter Compressor Refrigerant Amount charged at shipment Shipping Height x Width x Depth Height x Width x Depth 86 0 mm 4 Room Multi Outdoor Unit 230V 1 198 to 264 27 300 9 4 32 100 Cooling Heating 1 kg kg 890 x 900 x 320 82 0 V Refrigerant Control mm 6 35...

Страница 12: ...se Heater Control PCB Safety Device Rough Measure RPM Cool Hi Heat Hi Run Capacitor Type Model Q ty No of Poles W Ohm Nominal Output Coil Resistance 50 750 750 BLU RED 77 5 CB CMRV1424EH Part No Fan Motor Type Compressor Model Nominal Output Compressor Oil Amount Coil Resistance Ambient Temp 20 o C Yes Heat Exchanger Coil Microprocessor 250V 25A Control Circuit Fuse Controls 1 D420 Fan Propeller A...

Страница 13: ...s W Ohm 8 Nominal Output Coil Resistance 90 750 750 Control PCB CB CMRV1924EH Part No Fan Motor Type Compressor Model Nominal Output Compressor Oil Amount Coil Resistance Ambient Temp 20 o C 230V 25W Heat Exchanger Coil Microprocessor 250V 25A Control Circuit Fuse Controls 1 D460 Fan Propeller Ambient Temp 20 o C SIC 71FW D490 1 1 Face Area m2 0 595 Coil Rows Fin Pitch mm Yes Internal Controller A...

Страница 14: ...Safety Device Yes Run Capacitor CS 7LN115 Open 115 o C Close 100 o C Yes Internal Controller Aluminum Plate Fin Copper Tube 2 1 4 Face Area m2 0 595 Coil Rows Fin Pitch mm Heat Exchanger Coil Microprocessor 250V 25A Control Circuit Fuse Controls 1 D460 Fan Propeller Ambient Temp 20 o C SIC 71FW D490 1 1 Control PCB CB CMRV1934EH Part No Fan Motor Type Compressor Model Nominal Output Compressor Oil...

Страница 15: ...s W Ohm 8 Nominal Output Coil Resistance 90 750 750 Control PCB CB CMRV2444EH Part No Fan Motor Type Compressor Model Nominal Output Compressor Oil Amount Coil Resistance Ambient Temp 20 o C 230V 25W Heat Exchanger Coil Microprocessor 250V 25A Control Circuit Fuse Controls 1 D460 Fan Propeller Ambient Temp 20 o C SIC 71FW D490 1 1 Face Area m2 0 595 Coil Rows Fin Pitch mm Yes Internal Controller A...

Страница 16: ... Safety Device Yes Run Capacitor CS 7LN115 Open 115 o C Close 100 o C Yes Internal Controller Aluminum Plate Fin Copper Tube 2 1 4 Face Area m2 0 723 Coil Rows Fin Pitch mm Heat Exchanger Coil Microprocessor 250V 25A Control Circuit Fuse Controls 1 D460 Fan Propeller Ambient Temp 20 o C SIC 71FW D490 1 1 Control PCB CB CMRV3144EH Part No Fan Motor Type Compressor Model Nominal Output Compressor Oi...

Страница 17: ... sensor AW AN sensor BW BN sensor CW CN sensor DW DN sensor TKS295B TKS292B TKS292B TKS292B TKS292B TKS292B Model No of sensor Sensor Name 1 1 1 1 0 0 1 1 1 1 0 0 1 1 1 1 1 0 Quantity of Sensor 1 1 1 1 1 1 1 1 1 1 1 1 SAP CMRV1424EH SAP CMRV1924EH SAP CMRV1934EH SAP CMRV2444EH SAP CMRV3144EH Sensor Name Compressor temp sensor TKS293B Model No of sensor 1 1 1 Quantity of Sensor 1 1 SAP CMRV1424EH S...

Страница 18: ...90 70 46 336 310 285 4 I D 2 3 6 ID 18 2 I D 1 2 569 15 70 122 158 70 142 46 Wide tube service valve dia 9 52 3 8 2 Narrow tube service valve dia 6 35 1 4 2 Unit mm 3 DIMENSIONAL DATA Outdoor Unit SAP CMRV1424EH 18 ...

Страница 19: ...93 608 136 12 900 85 35 369 345 320 I D 1 8 5 I D 2 3 6 740 18 75 113 150 72 114 51 Wide tube service valve dia 9 52 3 8 2 Narrow tube service valve dia 6 35 1 4 2 Outdoor Unit SAP CMRV1924EH Unit mm 19 ...

Страница 20: ...608 136 12 35 369 345 320 I D 1 8 5 I D 2 3 6 900 85 740 18 75 70 113 150 72 70 114 51 Wide tube service valve dia 9 52 3 8 3 Narrow tube service valve dia 6 35 1 4 3 Outdoor Unit SAP CMRV1934EH Unit mm 20 ...

Страница 21: ...20 I D 1 8 5 I D 2 3 6 900 85 740 18 75 70 113 150 72 70 114 51 70 70 Wide tube service valve dia 9 52 3 8 3 Narrow tube service valve dia 6 35 1 4 4 Wide tube service valve dia 12 70 1 2 1 Outdoor Unit SAP CMRV2444EH Unit mm 21 ...

Страница 22: ...20 I D 1 8 5 I D 2 3 6 900 85 890 18 75 70 113 150 73 70 114 51 70 70 Wide tube service valve dia 9 52 3 8 2 Narrow tube service valve dia 6 35 1 4 4 Wide tube service valve dia 12 70 1 2 2 Outdoor Unit SAP CMRV3144EH Unit mm 22 ...

Страница 23: ... be a min 8 mm After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack Wide tube Thickness Min 8 mm Insulation Narrow tube Thickness Min 8 mm IMPORTANT CAUTION Compressor 4 way valve Main accumulator Sub accumulator Service valve on narrow tube Service valve on wide tube Wide tube BN AN BW AW O D 9 52mm O D 9 52mm Narrow tube O D 6 3...

Страница 24: ... insulation should be a min 8 mm After a tube has been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack Wide tube Thickness Min 8 mm Insulation Narrow tube Thickness Min 8 mm IMPORTANT CAUTION Compressor 4 way valve Main accumulator Sub accumulator Service valve on narrow tube Service valve on wide tube Wide tube BN AN BW AW O D 9 52mm O D 9 52mm H...

Страница 25: ... been insulated never try to bend it into a narrow curve because it can cause the tube to break or crack Wide tube Thickness Min 8 mm Insulation Narrow tube Thickness Min 8 mm IMPORTANT CAUTION Compressor 4 way valve Main accumulator Sub accumulator Service valve on narrow tube Service valve on wide tube Wide tube CN BN AN CW BW AW O D 9 52mm O D 9 52mm O D 9 52mm Narrow tube O D 6 35mm O D 6 35mm...

Страница 26: ... never try to bend it into a narrow curve because it can cause the tube to break or crack Wide tube Thickness Min 8 mm Insulation Narrow tube Thickness Min 8 mm IMPORTANT CAUTION Compressor 4 way valve Main accumulator Sub accumulator Service valve on narrow tube Service valve on wide tube Wide tube DN CN BN AN DW CW BW AW O D 9 52mm O D 9 52mm O D 9 52mm O D 12 7mm Narrow tube O D 6 35mm O D 6 35...

Страница 27: ... never try to bend it into a narrow curve because it can cause the tube to break or crack Wide tube Thickness Min 8 mm Insulation Narrow tube Thickness Min 8 mm IMPORTANT CAUTION Compressor 4 way valve Main accumulator Sub accumulator Service valve on narrow tube Service valve on wide tube Wide tube DN CN BN AN DW CW BW AW O D 9 52mm O D 9 52mm O D 12 7mm O D 12 7mm Narrow tube O D 6 35mm O D 6 35...

Страница 28: ...RMANCE DATA 5 1 Temperature Charts This data will be available in next issue of the Technical Service Manual 5 2 Heating Performance This data will be available in next issue of the Technical Service Manual 28 ...

Страница 29: ... BW THERMISTOR BN THERMISTOR 4P CONNECTOR BLU 1 2 3 4 W W YEL YEL YEL YEL YEL YEL YEL YEL 1 1 2 2 3 3 4 4 5 5 GRY GRY 5 5 5 4 4 BLK BLK 4 4 4 3 3 YEL YEL 3 3 3 2 2 RED RED 2 2 2 1 1 ORG ORG 1 1 1 DEF1 DEF0 2P CONNECTOR BLK BLK BLK BLU BLU DEF COIL DEFROST VALVE 2 2 1 1 W W RV1 RV0 2P CONNECTOR WHT BLK BLK BLU BLU RV COIL 4WAY VALVE 2 2 1 1 W W L2 L1 E 2 MV0 MAGNETIC COIL 5P CONNECTOR BLU MV1 FAN M...

Страница 30: ...HT RED PNK REACTANCE CONTROLLER BLK BLK WHT COIL OUTDOOR COIL THERMISTOR COMPRESSOR THERMISTOR RED 2P CONNECTOR OUTDOOR THERMISTOR COMP 1 2 3 4 1 2 1 2 YEL YEL BLK BLK 1 2 3 4 A TH AW THERMISTOR AN THERMISTOR 1 2 3 4 YEL YEL YEL YEL 1 2 3 4 B TH BW THERMISTOR BN THERMISTOR 1 2 3 4 W W YEL YEL YEL YEL 1 2 3 4 5 4 3 2 1 DEF1 DEF0 2P CONNECTOR BLK BLK BLK BLU BLU DEF COIL DEFROST VALVE 2 2 1 1 W W RV...

Страница 31: ...NIT C INDDOR UNIT POWER SUPPLY N L TO INDDOR UNIT WHT REACTANCE BLK BLK WHT BLK BLK BRN RED BLU WHT FERRITE CORE W ACIN1 W ACIN2 W SI A W SI B FERRITE CORE 3P CONNECTOR COMPRESSOR MOTOR C W S U R V WHT CM BLU WHT RED PNK BLU WHT RED PNK GRN YEL 1 2 3 3 2 1 CRANKCASE HEATER 2P CONNECTOR WHT WHT WHT WHT WHT 1 1 2 2 W W HEATER1 HEATER0 MAGNETIC COIL MV0 5 GRY 5 5 4 BLK 4 4 3 YEL 3 3 2 RED 2 2 1 ORG 1...

Страница 32: ...LK BLK WHT BLK BLK BRN GRY RED BLU FERRITE CORE W ACIN1 W ACIN2 W SI A W SI B FERRITE CORE 3P CONNECTOR COMPRESSOR MOTOR C W S U R V WHT CM BLU WHT RED PNK BLU WHT RED PNK GRN YEL 1 2 3 3 2 1 CRANKCASE HEATER 2P CONNECTOR WHT WHT WHT WHT WHT 1 1 2 2 W W HEATER1 HEATER0 MAGNETIC COIL MV0 5 GRY 5 5 4 BLK 4 4 3 YEL 3 3 2 RED 2 2 1 ORG 1 1 5 4 3 2 1 MV0 MAGNETIC COIL MV1 5 GRY 5 5 4 BLK 4 4 3 YEL 3 3 ...

Страница 33: ...T BLK BLK BRN GRY RED BLU FERRITE CORE W ACIN1 W ACIN2 W SI A W SI B FERRITE CORE 3P CONNECTOR 7P CONNECTOR COMPRESSOR MOTOR C W S U R V WHT WHT CM BLU WHT RED PNK BLU WHT RED PNK GRN YEL 1 2 3 3 2 1 CRANKCASE HEATER 2P CONNECTOR WHT WHT WHT WHT WHT 1 1 2 2 W W HEATER1 HEATER0 MAGNETIC COIL MV0 5 GRY 5 5 4 BLK 4 4 3 YEL 3 3 2 RED 2 2 1 ORG 1 1 5 4 3 2 1 MV0 MAGNETIC COIL MV1 5 GRY 5 5 4 BLK 4 4 3 ...

Страница 34: ...equency then increases The thermostat turns OFF The outdoor unit stops It does not stop if the thermostat for another indoor unit is ON Approximately 30 seconds after the thermostat turns OFF the indoor fan is stopped The indoor fan is stopped The indoor and outdoor temperatures are high The outdoor unit starts automatically after 3 minutes During these 3 minutes a low pressure pressure balance is...

Страница 35: ...tdoor unit is stopped and the temperature of the outdoor unit coil is at or below the L1 line Refer to Fig 1 All indicator lamps turn OFF The indoor and outdoor units stop The operating frequency during defrost is 80 Hz Frequency is lowered if the current peak cut off function is activated The maximum length of a single defrost operation is 12 minutes For the outdoor heat exchanger temperature con...

Страница 36: ...n was stopped it is assumed that there has been no significant change in the indoor and outdoor temperatures and the previous conditions COOL are stored Starts operating in the same operating mode COOL and with the same temperature settings as before operation was stopped Operation starts after 4 hours or more have passed New operating mode is determined based on the temperature conditions at the ...

Страница 37: ... is 15 C or higher and is slightly too cold The compressor operates on a 3 minutes ON 6 minutes OFF cycle to prevent the room temperature from dropping too much DRY operation starts DRY A operation The room temperature is below 15 C 1 f fluctuation fan 250 200 6 minute cycle Fig 2 150 100 Step 50 0 When monitoring operation begins the compressor stops and the indoor fan operates at LL very low spe...

Страница 38: ...rt of HEAT operation Compressor Outdoor fan Solenoid valve for hot gas bypass Temperature of the outdoor heat exchanger is at or above the temperature shown in the table below Temperature of releasing 1 The temperature for releasing of defrosting is 20 C or higher when the outdoor air temperature is less than 0 C Defrost operation time Coil temperature for releasing of defrosting Defrost operation...

Страница 39: ... Frequency Hz Trip Hz reduction Hz increase prohibit Hz reduction Hz increase prohibit Hz reduction Hz increase prohibit 16 15 6 0 30 Example of operation during cooling Frequency Frequency Current Stops operation Approx 3 minutes Power Point C Point B Point A 20A 17A 16 6A Target frequency Operates at the target frequency at Point A and below Stops increases to the frequency between Points A and ...

Страница 40: ...ip 5Hz every 30 sec reduction 2Hz every 30 sec reduction No control Increase prohibit range Hz reduction C Compressor discharge temperature 90 Within the increase prohibit range the range changes to the Hz reduction range 2 Hz every 30 seconds if the compressor temperature rises by 2 C Operation starts at 8 Hz and the start current is less than the normal operating current This prevents the flicke...

Страница 41: ...n after the power is turned OFF and some time is required for the charge to dissipate Be careful not to touch any electrified parts before the control circuit board Power Lamp red turns OFF If the outdoor control circuit board is normal approximately 180 seconds will be required for the charge to dissipate However allow at least 30 minutes for the charge to dissipate if it is thought there might b...

Страница 42: ... the nature of the trouble Heat Exchanger Rear side P C Board of Electrical Component Box Error Monitor Lamps Front side Fig 1 View from top ERR0 ERR1 ERR2 ERR3 Power Lamp Error Monitor Lamp Error Contents ERR0 ERR1 ERR2 ERR3 Sensor for compressor discharge temp Sensor for heat excharge temp Sensor for branch pipe A Narrow tube Sensor for branch pipe B Narrow tube Sensor for branch pipe C Narrow t...

Страница 43: ... the outdoor coil temperature sensor connector Non stop defrost The maximum lenght of defrost operation is 12 minutes Defrost can also be released based on the below conditions for the outdoor heat exchanger sensor However the condition is 20 C or higher when the outdoor air temperature is below 0 C Less than 2 minutes Not released 2 minutes or more 14 C or higher No 1 Check items unit operation I...

Страница 44: ...e Coil thermistor Electric expansion valve Branch tubing temperature sensor Breaker Refrigerant gas pressure 1 2 3 4 5 6 7 8 9 10 Operation lamp blinking Operation lamp does not illuminate Indoor fan dose not turn Outdoor unit does not operate Outdoor fan dose not turn 4 way valve does not operate The compressor only does not operate The compressor stops on occasion The compressor speed does not i...

Страница 45: ... close the electric expansion valve by hand to check it Replace the electric expansion valve This part is normal Check elsewhere Check the illumination of the red LED Replace the controller Check the coil resistance Use a tester to measure the voltage 12 V Model No Sequence SAP CMRV1424EH SAP CMRV1924EH SAP CMRV2444EH SAP CMRV3144EH SAP CMRV1934EH MV0 MV1 When the power is turned ON the needle wil...

Страница 46: ... pressure in the low pressure section is 5 MPa or more below the value in the performance charts 2 There is little condensation on the indoor heart exchanger which overall appears dry Distinguishing between refrigerant shortage and refrigerant circuit blockage If the pressure in the low pressure section does not change when the circuit is charged 2 to 3 times with refrigerant gas 200 g each time o...

Страница 47: ...ptom 4 Fan motor rotation speed does not change during outdoor unit operation Trouble symptom 5 Fan motor rotation speed varies excessively during outdoor unit operation Remedy for symptom 3 to 5 It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble Therefore first replace the outdoor unit controller then if necessary replace the DC motor Important ...

Страница 48: ...ge the specified amount of refrigerant with the new refrigerant at its normal mixed composition state in liquid phase When refrigerant R410A is used the composition will differ depending on whether it is in gaseous or liquid phase and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in gaseous state Thus always charge the refrigerant while it ...

Страница 49: ...R22 and R407C No addition of compressor oil for R410A No additional charge of compressor oil is permitted No use of refrigerant other than R410A Never use a refrigerant other than R410A If refrigerant R410A is exposed to fire Through welding etc toxic gas may be released when R410A refrigerant is exposed to fire Therefore be sure to provide ample ventilation during installation work Caution in cas...

Страница 50: ...can be com monly used for R22 R407C and R410A CAUTION The above tools specifically for R410A must not be used for R22 and R407C Doing so will cause malfunction of the unit For the above vacuum pump 1 2 and vacuum pump adapter 3 those for R22 type units can be used for R410A type However they must be used exclusively for R410A and never alternately with R22 and R407C For details on tubing installat...

Страница 51: ...place it quickly 3 Checking for sealing Use nitrogen gas for the pressurized gas and never use a refrigerant other than R410A Also do not use oxygen or any flammable gas 4 Evacuation Use a solenoid valve installed vacuum pump so that even if power is cut off in the middle of evacuation of air due to a power interruption the valve will prevent the pump oil from flowing back The equipment may be dam...

Страница 52: ...frigerant cylinder use an electronic scale for charging refrigerant In this case if the volume of refrigerant in the cylinder becomes less than 20 of the fully charged amount the composition of the refrigerant starts to change Thus do not use the refrigerant if the amount in the charging cylinder is less than 20 Also charge the minimum necessary amount to the charging cylinder before using it to c...

Страница 53: ...ing flux and wax for R410A Prevent oxide film from forming inside the tubes utilizing substitution with nitrogen N2 in the refrigerant circuit of the unit Leave ends of tubes open during welding 4 Checking for sealing Use nitrogen gas for the pressurized gas and never use a refrigerant other than R410A Also do not use oxygen or any flammable gas 5 Evacuation Use a solenoid valve installed vacuum p...

Страница 54: ...410A for existing units which use R22 This will cause the air conditioner to operate improperly and may result in a hazardous condition 9 8 2 Use of Existing Tubing If replacing an older unit that used refrigerant R22 with a R410A unit do not use its existing tubing Instead completely new tubing must be used CAUTION Never charge additional refrigerant if refrigerant is leaking from the unit Follow...

Страница 55: ...INSTALLATION INSTRUCTIONS SAP CMRV1424EH II 852 6 4190 206 00 0 APPENDIX A A 1 ...

Страница 56: ... How to Connect Wiring to the Terminal 5 5 Wiring Instructions for the Outdoor Unit 6 TEST RUN 18 7 CONNECTING A HOME AUTOMATION DEVICE 19 8 INSTALLATION CHECK SHEET 19 9 ELECTRIC WIRING DIAGRAM 20 INSTALLATION INSTRUCTIONS Model Combinations Combine indoor and outdoor units only as listed below Indoor Unit Outdoor Unit SAP KMRV74EH SAP CMRV1424EH SAP KMRV94EH SAP KMRV124EH Combine indoor and outd...

Страница 57: ...d outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fin gers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulat...

Страница 58: ...nsulation Consult your nearest sales outlet or A C workshop 1 4 Type of Copper Tube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2 Cut each tube to the appropriate lengths 30 cm to 40 cm to dampen vibration between units Table 2 2 Foamed polyethylene insulat...

Страница 59: ... High on a wall is best G select a location that will hold the weight of the unit G select a location where tubing and drain hose have the shortest run to the outside Fig 1 G allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 2 G install the unit within the maximum elevation difference H1 H2 above or below the outdoor unit and within a total tubing length...

Страница 60: ...operating noise Table 3 unit mm 2 2 Connecting Indoor Units 1 Connecting indoor unit for SAP CMRV1424 Fig 4 ø9 52 ø6 35 ø9 52 ø6 35 ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV74EH KMRV94EH KMRV124EH Max Allowable Max Allowable Limit of Limit of Elevation Required Amount Model Tubing Length Total Tubing Length Total Tubing Length Difference of Additional per un...

Страница 61: ...vel to reduce humidity and protect the unit against possible water damage and decreased service life Fig 5c G Install cushion rubber under unit s feet to reduce vibration and noise Fig 5d G use lug bolts or equal to bolt down unit reducing vibration and noise G Install in a location where no antenna of a television or radio exists within 3 meters Outdoor unit Hot air Heat source Exhaust fan NO Fig...

Страница 62: ...e caution Connecting any other model may result in operation failure and malfunction The dimensions indicated by in the figure below are spaces that are required in order to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In principle the top direction should be unobstructed Indoor unit B Indoor unit A ...

Страница 63: ...or and outdoor units In this method the copper tubes are flared at each end and connected with flare nuts 3 4 Flaring Procedure with a Flare Tool 1 Cut the copper tube to the required length with a tube cutter It is recommended to cut approx 30 50 cm longer than the tubing length you estimate 2 Remove burrs at the end of the copper tube with a tube reamer or file This process is important and shou...

Страница 64: ...r proper connection align the union tube and flare tube straight with each other then screw in the flare nut lightly at first to obtain a smooth match Fig 13 3 6 Tubing Connections a Temporary connection Screw in 3 5 rotations by hand Fig 14 b To fasten the flare nuts apply specified torque as Table 4 NOTE NOTE Reamer Copper tubing Fig 9 Flare tool Flare nut Copper tubing Fig 11 Fig 10 Apply refri...

Страница 65: ...p approx every 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the con densation drain hose splits away from the bundle and drips clear of the unit and the tubing 3 9 Finishing the Installation After finishing insulating and taping over the tubing use sealing putty to seal off the hole in the wall to prevent rain and draft from ente...

Страница 66: ...t run has been completed Note that both narrow and wide tube service valves on the outdoor unit are kept closed at this stage 2 Using an adjustable wrench or box wrench remove the valve caps from the service valve on both narrow and wide tubes 3 Connect a vacuum pump and a manifold valve with pressure gauges to the service port on the wide tube service valve Fig 20 Fig 20 Fig 21 CAUTION Be sure to...

Страница 67: ...k then apply the vacuum again 6 With a hex wrench turn the valve stem on the nar row tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again 7 With a standard screwdriver turn the wide tube service valve stem counterclockwise to fully open the valve 8 Turn the narrow tube service valve stem counter clockwise to fully open the va...

Страница 68: ...on Pump down procedure 1 Fully close the spindles at the valves on the narrow tube side of tubes A and B Refer to Fig 22 2 Connect the manifold gauge to the charging port at the valve on the wide tube side of tube B Purge the air from the charging hose Refer to Fig 23 3 Perform cooling operation or forced cooling operation When the pressure at the low pressure side is 0 15 0 2 MPa 0 5 1 kg cm2 G f...

Страница 69: ...h the refrigerant tubing compressor or any moving parts of the fan 6 Unauthorized changes in the internal wiring can be very dangerous The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes 5 2 Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality For field wiring requirements...

Страница 70: ...ny closer than 1 meter from the power cable and wires between the indoor and outdoor units Electrical noise may affect the operation G To avoid the risk of electric shock each air conditioner unit must be grounded G For the installation of a grounding device please observe local electrical codes G Grounding is necessary especially for units using inverter circuits in order to release charged elect...

Страница 71: ...minal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver I For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends Figs 28 and 29 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 ...

Страница 72: ...unction if the wiring connections are incorrect A is the indoor unit with refrigerant tubing that is connected to service valve A top of the outdoor unit refrigerant tubing that is connected to service valve B top of the outdoor unit B is the indoor unit with 5 5 Wiring Instructions for the Outdoor Unit G Be sure to correctly align inter unit cables A and B G Use a dedicated A C circuit for power ...

Страница 73: ...r unit If 2 units are operated simultaneously it is not possible to correctly check for errors in tubing and wiring G If the room temperature is 15 C or below it may not be possible to check for tubing errors with cooling operation If this occurs perform heating operation for each unit individually and check that warm air is dis charged from each unit If there is cold air mixed in with the warm ai...

Страница 74: ...e power and voltage are as specified Inter unit cables are securely fastened to the terminal board Inter unit cables are securely fixed The power cord and inter unit cables are not connected anywhere along their paths The ground wire is securely connected An air purge of the refrigerant circuit has been conducted A leak test of the tubing connections has been performed Thermal insulation has been ...

Страница 75: ...BLK BLK W W ACIN1 W BLK WHT RED 25A ACIN2 W W W S1 A S1 B BLU BLK WHT WHT BLK BLK REACTANCE 1 2 3 4 5 6 7 8 GND POWER SUPPLY B INDOOR UNIT A INDOOR UNIT TO INDOOR UNIT CONTROLLER W W WHT WHT BLK BLK WHT WHT 2P CONNECTOR 2P CONNECTOR 4P CONNECTOR 3P CONNECTOR 7P CONNECTOR WHT WHT 4P CONNECTOR RED 4P CONNECTOR BLU BLU RED 5P CONNECTOR 5P CONNECTOR W U W V W W DCFM CN04 FERRITE CORE WHT BLU RED PNK W...

Страница 76: ...INSTALLATION INSTRUCTIONS SAP CMRV1924EH SAP CMRV1934EH SAP CMRV2444EH SAP CMRV3144EH II 852 6 4189 992 00 2 APPENDIX B A 2 ...

Страница 77: ...tions for the Outdoor Unit 6 TEST RUN 23 7 CONNECTING A HOME AUTOMATION DEVICE 24 8 INSTALLATION CHECK SHEET 24 9 ELECTRIC WIRING DIAGRAM 25 INSTALLATION INSTRUCTIONS Model Combinations Combine indoor and outdoor units only as listed below Indoor Unit Outdoor Unit SAP KMRV74EH SAP CMRV1924EH SAP KMRV94EH SAP CMRV1934EH SAP KMRV124EH SAP CMRV2444EH SAP KRV184EH SAP CMRV3144EH SAP KRV244EH Combine i...

Страница 78: ...d outdoor units Get a partner to help and bend your knees when lifting to reduce strain on your back Sharp edges or thin aluminum fins on the air conditioner can cut your fin gers When Installing In a Ceiling or Wall Make sure the ceiling wall is strong enough to hold the unit s weight It may be necessary to construct a strong wood or metal frame to provide added support In a Room Properly insulat...

Страница 79: ...ube and Insulation Material If you wish to purchase these materials separately from a local source you will need 1 Deoxidized annealed copper tube for refrigerant tubing as detailed in Table 2 Cut each tube to the appropriate lengths 30 cm to 40 cm to dampen vibration between units Table 2 2 Foamed polyethylene insulation for the specified copper tubes as required to precise length of tub ing Wall...

Страница 80: ...a location that will hold the weight of the unit G select a location where tubing and drain hose have the shortest run to the outside Fig 1 G allow room for operation and maintenance as well as unrestricted air flow around the unit Fig 2 G install the unit within the maximum elevation difference H1 H2 H3 H4 above or below the outdoor unit and within a total tubing length L1 L2 L1 L2 L3 L1 L2 L3 L4...

Страница 81: ...lare A joint for connecting tubes of different sizes ø9 52 ø12 70 Supplied Reducer ø9 52 ø6 35 ø12 70 ø6 35 ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KRV184EH Fig 4 ø9 52 ø6 35 ø9 52 ø6 35 ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV74EH KMRV94EH KMRV124EH A B Max Allowable Max Allowable Total Limit of Limit of Elevation Requi...

Страница 82: ...t for SAP CMRV2444 unit mm A Fig 4b ø9 52 ø9 52 ø6 35 ø9 52 ø6 35 ø9 52 ø6 35 C ø9 52 B ø9 52 A Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV74EH KMRV94EH KMRV124EH B Fig 4c ø12 70 Union ø9 52 Flare A joint for connecting tubes of different sizes ø9 52 ø12 70 Supplied Reducer ø9 52 ø9 52 ø6 35 ø9 52 ø6 35 ø12 70 ø6 35 C ø9 52 B ø9 52 A Outdoor un...

Страница 83: ...2 70 ø6 35 ø15 88 ø6 35 C ø9 52 B ø12 70 A SAP KRV184EH SAP KMRV74EH KMRV94EH KMRV124EH ø9 52 ø9 52 ø6 35 D Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KRV244EH ø12 70 Union ø9 52 Flare ø9 52 ø12 70 Locally purchased C Fig 4f ø15 88 Union ø12 70 Flare ø12 70 ø15 88 Locally purchased ø9 52 ø9 52 ø6 35 ø9 52 ø6 35 ø15 88 ø6 35 C ø9 52 B ø12 70 A SAP KMRV74EH KMRV94EH KMRV124EH SAP K...

Страница 84: ...ndoor unit for SAP CMRV3144 B Fig 4i ø9 52 Union ø12 70 Flare ø12 70 ø9 52 Supplied Reducer ø9 52 ø9 52 ø6 35 ø9 52 ø6 35 ø12 70 ø6 35 C ø12 70 B ø12 70 A SAP KMRV74EH KMRV94EH KMRV124EH SAP KMRV74EH KMRV94EH KMRV124EH ø9 52 ø9 52 ø6 35 D Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KRV184EH C Fig 4j ø9 52 ø9 52 ø6 35 ø12 70 ø6 35 ø12 70 ø6 35 C ø12 70 B ø12 70 A SAP KRV184EH SAP K...

Страница 85: ...ø9 52 ø6 35 D Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KRV244EH ø9 52 Union ø12 70 Flare ø12 70 ø9 52 Supplied Reducer E Fig 4l ø15 88 Union ø12 70 Flare ø12 70 ø15 88 Locally purchased ø9 52 ø9 52 ø6 35 ø12 70 ø6 35 ø15 88 ø6 35 C ø12 70 B ø12 70 A SAP KRV184EH SAP KMRV74EH KMRV94EH KMRV124EH ø9 52 ø9 52 ø6 35 D Outdoor unit Indoor unit SAP KMRV74EH KMRV94EH KMRV124EH SAP KRV2...

Страница 86: ...vel to reduce humidity and protect the unit against possible water damage and decreased service life Fig 5c G Install cushion rubber under unit s feet to reduce vibration and noise Fig 5d G use lug bolts or equal to bolt down unit reducing vibration and noise G Install in a location where no antenna of a television or radio exists within 3 meters Outdoor unit Hot air Heat source Exhaust fan NO Fig...

Страница 87: ... 75 73 70 70 70 70 A Service valve on narrow tube side Outer diameter ø6 35 Service valve on wide tube side Outer diameter ø12 70 Service valve on wide tube side Outer diameter ø9 52 A 608 136 12 900 345 320 369 85 740 18 150 72 70 51 113 75 70 114 A Service valve on narrow tube side Outer diameter ø6 35 Service valve on wide tube side Outer diameter ø9 52 A Fig 6d unit mm Fig 6c Fig 6b 1 SAP CMRV...

Страница 88: ...e below are spaces that are required in order to maintain performance Install in a location where the dimensions indicated by are ensured and where 2 or more faces of the unit are unobstructed In principle the top direction should be unobstructed Indoor unit C Indoor unit B Indoor unit A Indoor unit D Service space Power breaker Ground wire not provided Ensure 15cm of space if a drain hose is to b...

Страница 89: ...or and outdoor units In this method the copper tubes are flared at each end and connected with flare nuts 3 4 Flaring Procedure with a Flare Tool 1 Cut the copper tube to the required length with a tube cutter It is recommended to cut approx 30 50 cm longer than the tubing length you estimate 2 Remove burrs at the end of the copper tube with a tube reamer or file This process is important and shou...

Страница 90: ... proper connection align the union tube and flare tube straight with each other then screw in the flare nut lightly at first to obtain a smooth match Fig 13 3 6 Tubing Connections a Temporary connection Screw in 3 5 rotations by hand Fig 14 b To fasten the flare nuts apply specified torque as Table 4 NOTE NOTE Reamer Copper tubing Fig 9 Flare tool Flare nut Copper tubing Fig 11 Fig 10 Apply refrig...

Страница 91: ...p approx every 120 cm Do not wind the armoring tape too tightly since this will decrease the heat insulation effect Also be sure the con densation drain hose splits away from the bundle and drips clear of the unit and the tubing 3 9 Finishing the Installation After finishing insulating and taping over the tubing use sealing putty to seal off the hole in the wall to prevent rain and draft from ente...

Страница 92: ... on the wide tube service valve Fig 20 Fig 20 Fig 21 CAUTION Be sure to use a manifold valve for air purging If it is not available use a stop valve for this purpose The Hi knob of the manifold valve must always be kept closed CAUTION CAUTION Before using the vacuum pump adapter read the vacuum pump adapter manual and use the adapter correctly In order to prevent charging errors with A C that uses...

Страница 93: ...k then apply the vacuum again 6 With a hex wrench turn the valve stem on the nar row tube service valve counter clockwise by 90 degrees 1 4 turn for 10 seconds and then turn the stem clockwise to close it again 7 With a standard screwdriver turn the wide tube service valve stem counterclockwise to fully open the valve 8 Turn the narrow tube service valve stem counter clockwise to fully open the va...

Страница 94: ... problem 4 Disconnect the manifold gauge and the inter unit tubes and attach the caps and flare nuts At this point pump down is completed If the caps and flare nuts are not reattached there is the danger of gas leakage Refer to Fig 24 If pump down is not possible If the A C cannot be operated because of a malfunction or other cause use a refrigerant recovery device to recover the refrigerant In or...

Страница 95: ... moving parts of the fan 6 Unauthorized changes in the internal wiring can be very dangerous The manufacturer will accept no responsibility for any damage or misoperation that occurs as a result of such unauthorized changes 5 2 Recommended Wire Length and Diameter Regulations on wiring diameter differ from locality to locality For field wiring requirements please refer to your local elec trical co...

Страница 96: ... electrical noise caused by high tension Otherwise electrical shock may occur G Place a dedicated ground more than 2 meters away from other grounds and do not have it shared with other electric appliances WARNING Fig 25b 4 indoor units with SAP CMRV2444 CMRV3144 1 2 3 Terminal INDOOR UNIT 1 2 3 INDOOR UNIT 1 2 3 4 4 4 1 UNIT B 2 3 4 UNIT C 5 6 7 8 9 1 2 3 Terminal Terminal L N INDOOR UNIT UNIT A A...

Страница 97: ...minal screw 4 Shape the loop wire properly place it on the termi nal plate and fix it securely with the removed termi nal screw using a screwdriver I For stranded wiring 1 Cut the wire end with a cutting pliers then strip the insulation to expose the stranded wiring about 10 mm and tightly twist the wire ends Figs 28 and 29 2 Using a screwdriver remove the terminal screw s on the terminal plate 3 ...

Страница 98: ... unit with refrigerant tubing that is connected to service valve A top of the outdoor unit refrigerant tubing that is connected to service valve B top of the outdoor unit B is the indoor unit with refrigerant tubing that is connected to service valve C top of the outdoor unit C is the indoor unit with refrigerant tubing that is connected to service valve D top of the outdoor unit D is the indoor u...

Страница 99: ...r unit If 2 units are operated simultaneously it is not possible to correctly check for errors in tubing and wiring G If the room temperature is 15 C or below it may not be possible to check for tubing errors with cooling operation If this occurs perform heating operation for each unit individually and check that warm air is dis charged from each unit If there is cold air mixed in with the warm ai...

Страница 100: ...e power and voltage are as specified Inter unit cables are securely fastened to the terminal board Inter unit cables are securely fixed The power cord and inter unit cables are not connected anywhere along their paths The ground wire is securely connected An air purge of the refrigerant circuit has been conducted A leak test of the tubing connections has been performed Thermal insulation has been ...

Страница 101: ... 2 1 REACTANCE COIL THERMISTOR COMP COIL OUTDOOR A TH B TH COMPRESSOR THERMISTOR OUTDOOR THERMISTOR AW THERMISTOR W W DEF1 DEF0 W W RV1 RV0 DEF COIL DEFROST VALVE 2 1 2 1 RV COIL 4WAY VALVE AN THERMISTOR BN THERMISTOR BW THERMISTOR BLK 2P CONNECTOR WHT 2P CONNECTOR 2 1 2 1 YEL YEL YEL YEL YEL YEL YEL YEL BLK BLK BLU BLU BLK BLK BLU BLU YEL YEL BLK BLK BLK BLK 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 ...

Страница 102: ...am for 3 room multi outdoor unit CMRV1934EH WHT WHT L2 L1 WHT WHT WHT 2P CONNECTOR 2 1 2 1 REACTANCE W W HEATER1 HEATER0 CRANKCASE HEATER COIL THERMISTOR COMP COIL OUTDOOR A TH B TH COMPRESSOR THERMISTOR OUTDOOR THERMISTOR AW THERMISTOR W W DEF1 DEF0 W W RV1 RV0 DEF COIL DEFROST VALVE 2 1 2 1 RV COIL 4WAY VALVE AN THERMISTOR BN THERMISTOR BW THERMISTOR BLK 2P CONNECTOR WHT 2P CONNECTOR 1 1 2 2 2P ...

Страница 103: ...ombination Table Name of Combination Table 2 Room Outdoor Unit Combination Table 2 Room Outdoor Unit Combination Table 3 Room Outdoor Unit Combination Table 4 Room Outdoor Unit Combination Table 4 Room Outdoor Unit Combination Table Model No of Outdoor Unit SAP CMRV1424EH SAP CMRV1924EH SAP CMRV1934EH SAP CMRV2444EH SAP CMRV3144EH Remarks OI 852 6 4180 810 00 0 OI 852 6 4180 865 00 0 OI 852 6 4180...

Страница 104: ...utdoor unit C 4 kW Rated cooling capacity of indoor units K1 K2 kW Then It is therefore possible to connect two units with respective capacities of 3 5 3 5 However since this combination is not found in the 2 room operation column of Table 1 operating all these units concurrently may result in trouble At a time like this shut down at least one of the two indoor units to match one of the combinatio...

Страница 105: ... 1 5 4 2 2 2 2 2 4 4 1 8 1 8 3 6 2 0 4 5 2 1 2 1 4 2 2 0 5 0 2 2 2 65 4 85 1 68 2 02 3 7 2 0 4 8 1 72 2 48 4 2 2 0 5 0 2 2 3 5 5 7 1 51 2 39 3 9 2 0 4 9 1 64 2 76 4 4 2 2 5 3 2 65 2 65 5 3 2 2 4 0 2 0 5 0 2 25 2 25 4 5 2 2 5 5 2 65 3 5 6 15 1 72 2 28 4 0 2 1 5 0 2 08 2 42 4 5 2 4 5 5 Combinations of operatable indoor units SAP CMRV1424EH Rated cooling capacity 4 0 kW 2 room Operation Total Perform...

Страница 106: ...unit C 5 6 kW Rated cooling capacity of indoor units K1 K2 kW Then It is therefore possible to connect two units with respective capacities of 5 15 5 15 However since this combination is not found in the 2 room operation column of Table 1 operating all these units concurrently may result in trouble At a time like this shut down at least one of the two indoor units to match one of the combinations ...

Страница 107: ...3 6 6 1 2 1 7 5 2 2 3 5 5 7 1 97 3 13 5 1 2 0 6 7 2 4 3 9 6 3 2 1 8 3 2 2 5 15 7 35 1 65 3 85 5 5 2 1 6 8 2 03 4 87 6 9 2 4 8 4 2 65 2 65 5 3 2 50 2 50 5 2 0 6 3 3 2 3 2 6 45 2 3 8 4 2 65 3 5 6 15 2 24 2 96 5 2 2 1 6 8 3 07 3 58 6 65 2 3 8 4 2 65 5 15 7 8 1 9 3 7 5 6 2 1 6 8 2 74 4 56 7 3 2 4 8 4 3 5 3 5 7 2 7 2 7 5 4 2 0 6 8 3 45 3 45 6 9 2 3 8 4 3 5 5 15 8 65 2 27 3 33 5 6 2 1 6 8 3 01 4 29 7 3 ...

Страница 108: ...it C 5 6 kW Rated cooling capacity of indoor units K1 K2 kW Then It is therefore possible to connect three units with respective capacities of 2 2 3 5 5 15 However since this combination is not found in the 3 room operation column of Table 1 operating all these units concurrently may result in trouble At a time like this shut down at least one of the three indoor units to match one of the combinat...

Страница 109: ...77 1 77 5 3 2 5 6 8 2 18 2 18 2 18 6 55 2 7 8 4 2 2 2 2 2 65 7 05 1 69 1 69 2 03 5 4 2 9 6 8 2 02 2 02 2 91 6 95 3 8 4 2 2 2 2 3 5 7 9 1 56 1 56 2 48 5 6 2 9 6 8 1 94 1 94 3 26 7 15 3 2 8 4 2 2 2 2 5 15 9 55 1 29 1 29 3 02 5 6 2 9 6 8 1 66 1 66 3 98 7 3 3 4 8 4 2 2 2 65 2 65 7 5 1 63 1 96 1 96 5 55 2 9 6 8 1 88 2 71 2 71 7 3 3 4 8 4 2 2 2 65 3 5 8 35 1 48 1 78 2 35 5 6 2 9 6 8 1 77 2 55 2 98 7 3 3...

Страница 110: ... 6 8 kW Rated cooling capacity of indoor units K1 K2 kW Then It is therefore possible to connect four units with respective capacities of 2 2 2 2 2 2 5 15 However since this combi nation is not found in the 4 room operation column of Table 1 operating all these units concurrently may result in trouble At a time like this shut down at least one of the four indoor units to match one of the combinati...

Страница 111: ... 3 79 8 3 3 2 9 0 2 2 2 2 5 15 9 55 1 57 1 57 3 67 6 8 2 9 8 1 1 95 1 95 4 69 8 6 3 4 9 0 2 2 2 65 2 65 7 5 1 97 2 4 2 4 6 7 2 9 8 1 2 16 3 12 3 12 8 4 3 4 9 0 2 2 2 65 3 5 8 35 1 79 2 16 2 85 6 8 2 9 8 1 2 06 2 97 3 47 8 5 3 4 9 0 2 2 2 65 5 15 10 1 5 1 8 3 5 6 8 2 9 8 1 1 78 2 56 4 26 8 6 3 4 9 0 2 2 3 5 3 5 9 2 1 63 2 59 2 59 6 8 2 9 8 1 1 97 3 31 3 31 8 6 3 4 9 0 2 2 3 5 5 15 10 9 1 38 2 19 3 ...

Страница 112: ...nit C 8 kW Rated cooling capacity of indoor units K1 K2 kW Then It is therefore possible to connect four units with respective capacities of 2 2 2 2 3 5 7 1 However since this combina tion is not found in the 4 room operation column of Table 1 operating all these units concurrently may result in trouble At a time like this shut down at least one of the four indoor units to match one of the combina...

Страница 113: ...2 9 9 0 2 08 2 42 4 9 9 4 3 4 9 8 2 65 5 15 5 15 13 1 64 3 18 3 18 8 2 9 9 0 2 17 3 62 3 62 9 4 3 4 9 8 3 5 3 5 3 5 10 5 2 65 2 65 2 65 7 95 2 9 9 0 3 03 3 03 3 03 9 1 3 4 9 8 3 5 3 5 5 15 12 2 2 3 2 3 3 39 8 2 9 9 0 2 73 2 73 3 9 9 35 3 4 9 8 3 5 3 5 7 1 14 1 1 99 1 99 4 03 8 2 9 9 0 2 34 2 34 4 73 9 4 3 4 9 8 3 5 5 15 5 15 13 8 2 03 2 99 2 99 8 2 9 9 0 2 44 3 48 3 48 9 4 3 4 9 8 2 2 2 2 2 2 2 2 ...

Страница 114: ...SANYO Electric co Ltd Osaka Japan March 2006 Printed in Japan T ...

Отзывы: