![Sanyo SAP-C181A Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/sanyo/sap-c181a/sap-c181a_technical-and-service-manual_363682011.webp)
7
Outdoor Unit
SAP – C241A
Compressor
Type
Rotary (Hermetic)
Compressor model
C-R221H5S 80687145
Nominal output
W
2,200
Compressor oil ... Amount
cc
SUNISO 4GSD-T ... 1,350
Coil resistance (Ambient temp. 25°C)
Ω
C–R : 0.777
C–S : 2.408
Safety devices
Type
Internal protector
External(OLR T)
Overload relay
—
OL-D24
Operating temp.
Open
°C
Automatic opening
150±5
Close
°C
Automatic reclosing
63±11
Operating amp.(Ambient temp. 25°C)
—
Trip in 6 to 16 sec. at 59A
Run capacitor
µF
40.0
VAC
400
Crank case heater
—
Fan & Fan Motor
Type
Propeller
Q'ty ... Dia.
1 ... ø420
Fan motor model ... Q'ty
KFG6S-51D5P-S ... 1
No. of poles ... rpm (240 V, High)
6 ... 890
Nominal output
W
50
Coil resistance (Ambient temp. 20°C)
Ω
WHT-BRN : 56.09
WHT-YEL : 42.13
YEL-PNK : 15.99
Safety devices
Type
Internal protector
Operating temp.
Open
°C
130±8
Close
°C
Automatic reclosing
Run capacitor
µF
4.0
VAC
440
Heat Exch. Coil
Coil
Aluminum plate fin / Copper tube
Rows
2
Fin pitch
mm
1.2
Face area
m
2
0.499
External Finish
Acrylic baked-on enamel finish
DATA SUBJECT TO CHANGE WITHOUT NOTICE.